Two CTs 1600/1 and 35/1 are in series. while checking the
ratio test of a CT(1600/1),same 1600A will also pass
through the CT having ratio 35/1.
Will it be harmfull to the ct(35/1),if yes , what will
happen.CT secondary is shorted
Answer Posted / ullas
if 1600 ampere current is passed through the second ct
having turn ratio 35/1 the definitely it will be
damaged.,since the ratio test equipment takes few seconds
to indicate the ratio error the condition will be worst .
no doubt.
each ct have certain burden value indicated on it as 10va,
15 va etc.
consider the case of 35/1 ct. hhaving burden 10VA.
this means while 35A is passing through the primary 1A is
produced in the secondary. and and this current can create
a potential up to 10V.
then calculate the value of secondary current curresponts
to 1600A primary current.
the primary of 35/1 ct is not designed to meet 1600A. so it
shall be burn out.
if we keep the two cts as series connected and 35/1 cts
secondary shorted. then also primary winding of the 35/1 ct
will not withstand with the 1600A.( it will simply act as a
conductor because there is no secondary.
Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
How can I calculate ISF of current transformer?
what is PID control in VFD drives?
what is the difference between earth leakage and earth fault?
What is the important precuations need tocarried out while working with Electrolite in Battery PM?
Draw transformer phasor diagram.(full load,no load)
which is better to use svc or synchronous condenser why ?
What is the function of a neutral reactor.
How to test REF relay testing for LV panel as per Kahramaa standard?
What is the vector group of a transformer,how can it be found out?
Can anybody inform me about the pattern of ECIL GET( Graduate Engineers Trainee) interview for Electrical students? Will there be HR round as well? I thought of preparing for 2 to 3 subjects thoroughly. Will it be sufficient? Please share your thoughts.
What is meant by stator? What is meant by rotor?
hi I have done 3 yrs diploma in electrical engg after 10+2. I have 16 years of work experience into design proposals sales and engg application development in LV/MV swithcgear and sub station automation field. I want to apply for immigration to new zealand but I am not sure whether I qualify or not since I dont have a degree. Can anyone advice? Thanks Riz
how can I calculate charging current of cable/overhead conductor? what is roll of voltage in it ?
im working in one private compeny in gujarat. i was complet diploma electric in 2010 from gujarat technical board. now i want electric supervisor licence in gujarat but i dont't know when i apply? plz give me address of the licence dippartment office in gujarat. gandhinagar
What is the fault or needs to be done when frequency in ac drives is not changing?