We have a 12MW power plant & we inject 5-6MW power to
Orissa GRID. For this we have a 33KV/11KV switch yard
having 12.5MVA power transformer. Some times we draw power
during emergency. It is observed that during Export or
Import for load less than 500Kw the power factor is
decreasing to 0.3 . This is happening only during export or
import. During island condition TG power factor OK.Our
capacitor bank is provided with our Power plant auxilliary
load. Please suggest how I can we improve our power factor
during low load (GRID).
Answer Posted / velusamy
This problem can be solved by switching off all capacitor
banks during low load. we have faced Similar type of
problem in our cement plant loads which are fluctuating in
nature which causes export / import of power fluctuation(
loads go +500kw and - 500kw withing 1 or two seconds).
The main reason for this low power factor is due to
reactive power consumption of your 12.5 MVA power
transformer.
Is This Answer Correct ? | 2 Yes | 2 No |
Post New Answer View All Answers
1. A bomber drops a bomb from an aircraft flying at 2000 km/hr. at an altitude of 7km. The speed at which the bomb will strike the earth would be
Please send 110 kv sb station full single line drawing(sld)
what is p.s impedance measurement test in earthing transformer?
How to minimize the eddy current losses?
sir, Is their any measuring unit of knoking? please explian?
Explain bypass capacitor?
Would you recommend to replace all oil filled cables with xlpe cable for hv transmission with the current technolgy for xlpe cable?
In convertor can we use rectifier thyristor in place of invertor thyristor with explain.
how to select proper cable for ct wiring so that drop within the limit.
Define non-touching loop.
Do u know any one? how to find out in motor rated amps? formula?
How to calculate VCB rating for 33KV ,25 MW Power line?
STATE WORKING OF VACCUM CIRCUIT BRAKER?
Wt is the function of reactive power? How it generates & consume though resultant is zero?
Define phase lag and phase lead?