How to select a D.G set for calculated load of 110kW..?
Answer Posted / pillay
D.G if ac is rated in KVA.Usually the alternator is rated at 0.8 pf. So KW/PF=KVA. 110/0.8=137.9.KVA.
Now the D.G must have some spare power to take care of starting current and a bit of future expansion so we load the D.G at 75%.
137.9/.75=183.8KVA
Now you can buy the nearest available D.G in the market.
Maybe 175KVA or 185 KVA
Is This Answer Correct ? | 44 Yes | 8 No |
Post New Answer View All Answers
What are the components of feedback control system?
How short circuit MVA(Fault MVA) in a power system calculated for calculating number of earth plates ?
hai iam arunkumar. i have applied for an section enginner in rrb. i want lat 5 years solved question papers. if u have please sedn it to arun30682@gmail.com
what is different between relay and plc?
If we connect a motor and generator together (I mean that the generator gives the motor electricity and the motor gives the generator movement) regardless the losses. Will the generator still generate and the motor still move?
Does the motor power displayed on the Motor name plate is the mechnical power motor delivers or it is consumed power from the system?
Why sometime AVR and sometime Booster coil is used in Alternator? what is the diferance between AVR & Booster coil due to which they are selected
i want to know that what is the eligibility critaria for ongc exam?
Earth has zero potential then what would be the neutral potential ?
state the working principle of incondenscent tube?
Why do not we prefer non conventional sources of energy to conventional sources?
How I calculate the ELCB for circuit breakers?
Which level of the Transformer oil got dielectric strengh? And why?
Why does amplifier gain reduce?
Block diagram of Power line communication?