if we convert ampers into kw,which one formula use by
us,pls tell me?
Answer Posted / pillay
there is no one formula only.
there are some formulas that you must know,,
you must know how to use the correct one when you need it.
for DC power it is always just voltage x current = watts
for AC single phase it is always volt x current x pf = watts
for AC 3 phase it is root 3 x volt x current x pf = watts
the watts than you change to KW or MW if necessary.
this are all for real calculations. when you practice with it often than you will be able to give an estimate bcos the pf varies according to situation.
Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
We are designer please help me calculate the size of 11kv cables from step up transformer to M.V panel, total load is 5 mega watt distance 900 feet (used aluminum type cables) please provided formula for calculate the cable with example.
What is the significance of integral controller and derivative controller in a pid controller?
how do we calculate length of starting time and repeated starting of a direct online starter?
A 500 V shunt motor runs at its normal speed of 250rpm when the armature current is 200A. The resistance of the armature is 0.12 Ω. Calculate the speed when a resistance is inserted in the field reducing the shunt field to 80% of normal value and the armature current is 100A.
How to set a Zone 1 distance relay for distribution feeder?
what is the formula for calculating the phase clerance between two phases and phase to earth how to calculate the cable for a motor
we are going to install a solar PV site and how can we calculate PV Solar Panel Efficiency, can anybody tell me complete method for its calculation.
Please help me regarding my one concern. - During earth pit testing we noticed that the Clean earth pit and dirty earth pit showing continuity (Resistance value - 5ohm) . I want to know that if both earth pit have separate location and there is not internal looping between PIT then why such continuity is showing on it . Because of this issue the field side all earthing point showing short. In PLC panel we are providing two types of earthing cable which is coming from separate earth pit (Clean and Dirty earth pit) because of earth PIT showing short our PLC is not complying spec . please help regarding this issues.
What is meant by sag?
what is there inside an inverter and how it works?
WHAT IS THE TOTAL POWER GENERATION IN CHHATTISGARH?
When we use 3 terminal resistor?
need to make a report. Need to choose a 3phase induction motor. Load conditions motor will operate in : Maximum Load: 30 Kw Speed: 2950 rpm Ambient temp: 20 cent Supply voltage: 440V Frequency: 50Hz need to look for the safety factor when choosing the motor, went through catalouge found a few, but dont know how to choose the safety factor allowing an extra load something above 30 KW to avoid any harm.
upto how much low RPM we will run the commercial motor which is run through VFD without any problem occurs in motor.Motor rating Duty is S1 & RPM is 1400.
what is the transformer turn ratio formula and give some examples?