how much Amp we can put in 1200kva generator?
Answer Posted / mohamed ali
Dear there are use the Formula
I= KVA X 1000/1.732 X 440 X 0.8
100 % - 1669 Amps
80 % - 1335 Amps
So always put in Amps 80% mean 1335 Amps
Is This Answer Correct ? | 8 Yes | 0 No |
Post New Answer View All Answers
Do closed loops systems require manual input?
1. what is usage for power factor in industries?? 2.why we need to monitor power factor??
what is RFCT and Insulgard Relay & It's function?
why i can not use thimble on capacitor duty contactor
Why neutral is not used in three phases dol starter
11kV capacitor bank of rating 2.4KVAR, is charged with protective relays of only over current & Earth fault &.......without Over Voltage, Under Voltage & Neutral Displacement Relay. Is it advisable??
Does outdoor isolator loose connection cause short circuit current in that circuit? if yes then how ??
what is the voltage regulation for unity and zero power factor?
how to calculte capacitor range for single phase induction motors??pls tel
"TRANSFORMER MODELING AND ANALYSIS" MEANS WHAT AND WHICH TOPICS U READ IN THIS
Showing results for capital, machinery, stock,wages, carriage in words, salaries, factory rent, repairs, fuel and power, buildings, debtors, sales, purchases, creditors, return outwords, return inwords, drawings, discount allowed, discount receivable, office expenses, bills payable, bills receivable, cash in hand, cash at bank, office rent comes under debit or credit
kindly send me 11KV MV motor differential protection procedure by primary injection method.
Write the programming software name for LG, SIEMENS,Messung,AB
What will happen if i replace a inductive proximity switch with photo sensor in a machine?
The power supplied to a 33microF capacitor from a 120V, 60Hz source will be