What core magnetic balance test of transformer?
How to do this test in a three phase Star delta (star-LV,
Delta-HV) transformer?
How to measure and where to measure?
thanks and regards
Austin
Answer Posted / engr. ziaul ashraf shafi
Answer #5 is fine.. but i want to add something more..
normally this test is made in star side of the transformer.
the result should be varified like following:
1) if 2u-2n is fed by 230 volt.
- the nearest phase (2v-2n) will experience the 85% to 90%
of fed voltage at 2u-2n. (i mean 2v-2n = 195.5 to 207
volt). And the distant phase (2w-2n) will experience the
10% to 15% of fed voltage at 2u-2n. (i mean 2w-2n = 23 to
34.5 volt).
2) if 2v-2n is fed by 230 volt.
- then the fed pahase is middle phase, and both other phase
are magnetically in equal distance.. so the measured
voltages in 2u-2n or 2w-2n = 50 % (or 40 to 60 % is also
accaptable). so the 2u-2n or 2w-2n = 92v to 138v is
accaptable.
3) if 2w-2n is fed by 230 volt.
- the nearest phase (2v-2n) will experience the 85% to 90%
of fed voltage at 2w-2n. (i mean 2v-2n = 195.5 to 207
volt). And the distant phase (2u-2n) will experience the
10% to 15% of fed voltage at 2u-2n. (i mean 2w-2n = 23 to
34.5 volt).
*If the results are found beyond these above mentioned
limits then other tests (like open ckt test with rated
voltage) should be performed to be sure about core and
winding.
*You can measure and note down the current of each injected
phase. it will give u a signaficant idea about winding. if
the winding has an inter-tern short then the faulty phase
will draw comapretively large magnetizing current like 3A
or 5A, wheather other phases will draw 60mA to 100mA.
*Remember, the magnetic reluctance path of a core is not
lenier, so the result veries itself. But big differences
are remarkable.
*Sometime due to non-lenier characteristic of magnatic
circuit and the presense of harmonics in the fluxes of un-
excited phases, the algebric sum of induced volage in two
phases may not be equal to the applied voltage.
*if there is a turn to turn fault in any phase winding, the
faulty section will draw comparetively large magnatizing
current which will oppose the magnetic fluxes and will
result a very low induced voltage (tends to zero) in the
faulty phase.
*this test should be performed after demagnaizing the
transformer properly. slightly magnatized transformer (like
after insulation test) can give you an unexpacted and
distorted result of magnetic balance test.
Is This Answer Correct ? | 73 Yes | 3 No |
Post New Answer View All Answers
can u give me a brief idea about power line carrier communication ??
WHAT ARE THE EFFECTS OF SERIES RESONANCE AND PARALLEL RESONANCE ON THE CIRCUITS PARAMETERS?
What is the difference between electrical earthing and electrical grounding?
In which working principal temperature transmitter work.explain in detailed.
How REF protects transformer alone? explain with diagram.
Does all the output contacts (N/O as well as N/C) of a Numerical relay operate when relay receives a binary input/inputs or contacts are designated to specific logic input/inputs and only these contacts operate?
Dear all, I want to use Induction motor to open and close a 1 ton door. How much power do I need. Thanks
how works inductive &capacitive sensors?
How we can calculate the life of Lead acid battery
What is method of calculating the fault current for a MDB, 50KW, 3PH, 415V, 50HZ?
please explain how to do 'pole drop test' on generator?
You are of electrical field and you are going for software? Why
What is mathematical model of a control system?
i am going to attaned the engineer (disign)iterview at HAL please give me duid line
What are the factor to be consider for CT selection in 132kV substation?