What is the difference between double compression
Answer Posted / shirsendu saha
I don't think any of the above answers are completely correct.
Single compression and double compression glands are used on
the basis of area classification.those who are affiliated
with oil and gas sector they will easily understand about
area classification.in zone 0 where the presence of
hydrocarbon is obvious (IIC)double compression gland is used
because the flame path in case of double compression gland
is much more than in case of single compression gland. the
logic behind this is that if there is any explosion inside
the terminal box of the motor no flame should be able to
come out through the cable gland in order to prevent fire
hazards but where there is no presence of hydrocarbons i.e
no danger of fire hazards (IIA/ IIB)single compression glads
are used. it has nothing to do with mechanical strength.
even in case of lighting fixtures used in IIC zone double
compression glands are used.
Is This Answer Correct ? | 89 Yes | 13 No |
Post New Answer View All Answers
I PURCHASED A DEISEL GENARATOR SET OF AVR TYPE& RATING 125KVA BUT SOME TIMES THE OUTPUT VOLTAGE IS FLUCTUATING WHAT ARE THE PROBABLE REASONS GIVE ME
What will happend if given Vfd out put to step up transformer
Mention the disadvantages of low power factor? How can it be improved?
which is the most advanced form of SF6 BREAKER?Can we use other gases to quench the arc?
i have 90kw motor.so i choose connect cable .please what is parameter checked so please give to formula
Write a note on materials used as a fuse element.
Why do you have to use Protecion relay with the function MTB ( Mechanical Trip Button ) for electrical system.
Pl. give me checklist for installation & commissioning of machine tool.
if in 3-phase system voltage=440V,frequency=60Hz, current=400A. then if it is single phase then current=? and if it is single phasing then current=?
11000volt DG set carnt kaise banvay
why to use freewheeling diode ( diode in revers bias mode) across dc coil
A 3-phase IM is supplied from 50 Hz system. It runs at speed of 1440 rpm and slip equal to 4 %. Calculate number of pole pairs. A 1 B 6 C 2 D 3
how to introduce yourself
operation of protection relay watchdog contact?
State superposition theorem?