how can u determine size of the conductor by knowing the
voltage level
Answer Posted / naveen
Yes one could determine the size of the conductor by knowing
the voltage levels and some other factors too.Also the
maximum voltage that can safely be applied to any winding is
determined by the type and thickness of the insulation used.
When a better (and thicker) insulation is used between the
windings, a higher maximum voltage can be applied to the
windings.
To be more specific by equations,
VD= 2*K*I*L/ CSA
WHERE:
VD= VOLTAGE DROP
I= CURRENT
L= DISTANCE OF THE LOAD FROM THE OUTLET (IN FT)
K= 12 FOR COPPER AND 19 ALUMINUM (FOR MAXIMUM TEMP OF 75 DC)
CSA= CONDUCTOR CROSS SECTIONAL AREA IN CIRCULAR MILS.
Is This Answer Correct ? | 3 Yes | 3 No |
Post New Answer View All Answers
sugest any typical project ?
Draw a circuit diagram in which if button is open we can use socket and bulb as a series test circit and if button is close than simple we can use socket as any load purpose.
IF I KNOW THE AREA OF CROSS SECTION OFTHE WIRE , WATTAGE OF THE LOAD ,VOLTAGE SUPPLY WHAT IM GIVING TO THE LOAD AND ALSO POWER FACTOR OF LOAD ....... SO GIVE ME FOR WHAT AMOUNT OF CURRENT I SHOULD USE WHICH TYPE OF CABLE?
hi all i like to know vat is power plot in control systems also i want to know abt latest trends in electrical & electronics
in power generator normaly voltagr betwween esth to neutral is 0 but my work place generator show the volatge is 60v any body know why? thanks
LET ME NOW MORE ABOUT icu and ics for circuit breaker. how we calculate the rating of circuit breaker and i c u and ics values
EXPLAIN THE WORKING OF SERIES REACTOR IN HT CAPACITOR BANKS (FOR VOLTAGES & CURRENTS)
how is the incoming cable size calculated for a given current rating of a panel??
where rlc series ckt used?
could anybody able 2 send me jindal steels previous papers fr electrical steam....pls send 2 my id if possible....sirisha.shaik@gmail.com
what is the meaning of the symbol << >> put in transformer drawing
acb(AIR CIRCUIT BREAKER)NOT CHARGING AUTO
What do you mean by per capita requirement of electrical energy in india
Refernce currents are to be generated using refernce cueernts how can this be done??
A 100 kVA , 400 v/250 kv testing transformer has 8% leakage reactance and resistance on 100 KVA base . A cable has to be tested at 500 kv using the above transformer as a resonant transformer at 50 hz . if the charging current of the cable at 500 kv is 0.4 A find the series inductance required . Assume 2% resistance for the inductor to be used and the connecting leads . Neglect dielectric loss of hte cable . what will be the input voltage to the transformer ?