What the purpose of transient fault recoredr in substation
Answer Posted / thowsif_emerson
Transient Fault Records in Substation we are using a DDFR
(Distributed Digital Fault Recording) System:-
Transient Fault Records (also known as Oscillography
records) that are recorded in protection relays will be
retrieve by the DDFR and stored in its internal memory
space. All Transient Fault Records will be archived using a
naming convention that will make it easy for users to
relate the Transient Fault records with a particular
substation fault. Each record will be stored with a name
that includes the exact date and time that the record was
initially triggered. If the Transient Fault record was
originally recorded in the relay as a COMTRADE file, the
DDFR will store this record in its native format; if the
protection relay stores it’s record in another format, such
as a CSV file, the DDFR will automatically convert this
file into the COMTRADE-1999 format so that the record can
be analyzed using a standard COMTRADE viewer.
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
How to know any size of cable if there are not written on cable? Answer must be theurical not by experience.
any earth foult trip the relay but in welding time not trip by earth foult
What are the disadvantages of autotransformer?
How to calulate Locked rotor amper(LRA) for compressor type motors?
DIFFERENCE BETWEEN NORMAL TRAFO AND THRISTER TRAFO?
To prove the capacity of a 10MVA transforemr with 6.5% impedance by a short circuit test how much power is needed to inject an impedance voltage if we have to arrive for its rated current?
What is inrush current?
explain different types of d.c motors?
What is the use of lag compensator?
what is the difference between electrical choke and electronic choke?
If o/p power is doubled by how much does the sound increase
What is Faraday's law
how to set relay setting? and example calculation...
when ac current flows thru d coil of a contactr,it energizes,magnetic field attracts d contact of the coil...nw wont dt ac current in d contct induce current back on to d coil thru mutual inductance leading to high currnt in d coil
what's producer of XLPE cable laying in undergroung