Answer Posted / thowsif_emerson_csm team
Assumed the transformer vector group As DYn11;
1.1U1V1W-which is primary -Delta Connection
2.2U2V2W- Which is secondary-Star connection
3.join 1U& 2U terminals
4.Supply 1U-1V-1W 440v Measured
a.1U-1V
b.1V-1w
c.1W-1U
d.1W-2W
e.1V-2W
f.1V-2V
g.1W-2V
h.1U-2N
i.1V-2N
TO CHECK
1.1V-2W=1V-2V
2.1W-2V>1W-2W
3.1U-1V=1V-2N+1U-2N
From above check(1,2,3) the vector group of transformer is
tested.....
Is This Answer Correct ? | 12 Yes | 0 No |
Post New Answer View All Answers
What is fault clearing time for Current Limiting Moulded Case Circuit Breaker?.
what is effect of length of air gap on performance of dc motor and generator?
Types of test in Switchgears, MCC, NGR and DB's how it should be procced. Can anyone give me the details here or email me to pasuvaraj.k@gmail.com
At what speed an electric car can run with 2 HP motor of weighing 400 kg?
I have iti elec, 1st aid, and 5 yrs experience in 7.5 mw power plant. Am i eligeble for 11kv license in telangana state..when, how to apply for that.?
when elecromagnatic waves are propogated in a wave guide?
What is the procedure/activities to be taken to inject the current more than 2000A by using 2000A Loading Transformer?
How Calculet The UPS AH In Load
why we use circuit breakers for switching instead of normal switching device?
How to calculate the size of earth cable to earth the neutral of UPS ?
What are the advantages & disadvantages of a group electrive drive?
The moisture in air will condense at
why do motors burn out? I understand why adding parallel loads to a power source means more current moves through the circuit, and can destroy circuit elements by overheating. What about when you have a vaccuum cleaner intake flush against a floor, a room fan sitting directly against a wall, or a power drill trying to drill through something too hard?
How much minimum insulation required between 11kv/3.3kv transformer windings?
what is the basic construction diffrance between servo motor ans sqiralcage induction motor