Answer Posted / abo ibrahim
Active Power=1.732*Load Current*Line Voltage*P.F.
P.F=0.8.
Active Power= 30kw = 3o*1000= 30000w
Load Current= 30000\(1.732*440*0.8).
=49.21 Amp.