for 12KW motor which cable size has to select for ex.10
meter.
Answer Posted / phanendra babu
the selected cable should have the capability of
withstanding the over load /short ckt currents upto before
operating the protecting device. so assume 0.81 p.f,the load
current is given by apprx 20A .very safe working of copper
cable is 4A to 6A per 1sqmm ,so the size of the cable
suitable for 12kw motor is 6sqmm. copper cable or 16 sqmm
aluminum cable.
the above calculation is for lo current ratings if current
rating increases capacity will decrease.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
what is negative and zero impedance in 3 phase induction motor ??
How to calculate the copper in HT motors if KW, RPM & Voltage is given
How many types of interlocking use in screw type air compressor,make-Kaser(BSD MODEL)?
by using pump duty, how we will can calculate the motor duty(KW)? is there any standard or formula.
Explain how to determine capacitor tolerance codes?
How to Calculate The sag of OPGW in Transmission Line???
What is the difference between type1 and type2 relay protection co-ordination for motor feeders
Define norton equivalent circuit?
Define noise?
How To increase Knowledge Of boliler regarding To Only Electrical Field..
hi friend i am going too attend for hpcl in this month please help me by sending written test question papers i am in the stream of E.E.E
What are the advantages of using distance protection schemes as opposed to normal overcurrent/ earth fault protection on high voltage feeders.
what is efficient motors and how it is different from normal induction motors
if an insulated power and control cables of a running gas diesel gensets laid direct in an open trench i.e, trench bed is not rcc of a power house in which rain water, spillage water alwas exists and all power control cables remains submerged even when gas gensets of 480 kw each runningin on load. These power &control cables runs from power house to switchgear room through these trenches in which water remains most of the time. pl explain its merit & de-merit
Is there a diode made that works with AC 120 volt 20 amp? If so can it completely stop all current flow in 1 direction at all times?