110 KW MOTER DOL STATER 240SQ.MM CABLE MOTER AND STARTER
DISTANCE IS 110 METER WHAT IS VOTAGE IN MOTER END AND
SYSTEM VOTAGE IS 415 V HOW I CAN CALCULTE
Answer Posted / m s rana
Its depends on the cable manufacturer and type of cable
(XLPE/PVC), type of conductor(AL/CU), system
(underground/overhead) etc. Also you have to consider
derating factors like temperature,gap betwwen cables,
distance between cable trays etc(thease details are
provided in the catalogue).
Also the manufacturer provided mv/amp/km details from that
you can calculate the voltage drop. As per standard the
drop at receiving end should be +/- 3% of sending end
voltage.
But it is not engineering to run 110kw motor run to DOL
Starter It IS VERY HIGH LOAD & LONG DISTANCE higher losses
Is This Answer Correct ? | 2 Yes | 4 No |
Post New Answer View All Answers
Whether IP65 enclosure box blocks ventilation if driver for LED have to enclosed inside IP65 box
what is the difference between electrical and electronic choke?
how to calculate singlephase motor efficiency?
what is servo motor and how it works?
what are types of encoder
I am using submission of two ct in one and half scheme for 67/67N protection. Both CTs star point is grounded separately near ct box.Will two point ground give wrong tripping to 67/67N during fault or no matter.
What is distance between electrical panel to land ?
If any cable burnt how can we identify it burnt by high current of high voltage?
Application Comparison between 22KV (UE)and 33KV (E) system. Are we allowed to use 33KV (E) cable in lieu of 22KV (UE) cable. What are the technical disadvantages.
Name one of major transformer company in KSA ?
hr round
What is the difference between relays and contactor construction wise?
1600 KVA ka transformer hi aghar lt side par 800A aur voltage 420 ho to HT side ki cable ki rating keya ho gi?
If I have 3 essential main switch board and 3 incoming electricity ,but only 1 genset running is that possible.
WHY IS THE EARTH FAULT CURRENT ALWAYS LESS THAN THE NORMAL CURRENT??