On load tap changer (OLTC) explode?
Transformer
Vector group: Ynd11
Rated Power: 353MVA
Rated Current: 693A
Voltage:294/20KV

OLTC
Type: T III Y1000 110/c 12193w
Max Operation Current: 295A
Step Voltage: 550V
Arrangement in Tx windings: Y Connection

Problem: Damage of Unit 1 Generator Transformer On Load Tap
Changer (OLTC)

Description of Incident:
9.00 a.m. :- Generator No Load test on excitation system
started

10.30 a.m :- Carried out AVR change over
test

11.30 a.m :- Preparation for Generator Manual Synchronizing
test


12.00 a.m :- Manual Synshronizing test started.
Observed incoming generator voltage higher than running voltage.
CECR operator operated Generator Transformer OLTC to bring down
the incoming generator voltage

12.03 a.m :-Generator Transformer abnormal alarm operated at
Gen.Control Desk (CECR)
CECR operater at Generator transformer bay informed that the
transformer
oil splashed out from OLTC.
CECR operater informed that he heard explosion inside OLTC.
Observed Oil level & Oil Flow alaram operated at Tranformer
local annunciator.

12.05 am :- CECR operator 'Open Gen Field Breaker”

12.10 a.m. :- Elec1 team inspected the OLTC and found the
OLTC rupture disk was broken
and oil spilled at OLTC area.
- Elec1 found the OLTC top cover bulging.

Do anyone know why and possibility cause happen in this OLTC.

Answer Posted / sudheer

please check the OLTC inside
connections ,carefully .because some times the connector
plate rollers not touch properly. so the winding temp.
increases continuously and oil will over-heated.

Is This Answer Correct ?    1 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how we sesign the transformer give some specifion regarding design of transformers

1471


can we synchronize star system generators with delta system transmission line ? and how ?

2313


can u give me a brief idea about power line carrier communication ??

1394


why Induction Generators are not "Black start" ? and apart from WTGs where this types of generator are generally used?

2221


Explain few advantages of electric traction system?

590






How phase to phase voltage comes 440V.

1456


sir i have cleared the apti test of EIL held on 15th march and my interview will be in new delhi on 2nd june.i will be very much helpful if u help me regarding the type of interview questions comes at EIL.(URGENT.........PLZZZZZZZZZZ...............)

1562


how to calculate energy of 3-phase motor?

1558


either water sensor or flow meter,how we observe the water level, f any other equipment are in market ?

1423


I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?

1405


what is the purpose of using filters in a protective relaying scheme?

1764


i have done diploma and btech in EE and live in Chandigarh so kindly help me how can i make my competency certificate in my area.

1785


what is the safty of poly phase tranformer?

1640


In ht capacitor ckt we are using LBS Panel it having isolator with fuse, one of HT fuse flash over, so what is reason behind this event.

1585


What is the difference IN MCCB's between thermal magnetic and electronic tripping system ?

1546