Answer Posted / karanth.sp
The PF of the connected load to a particular transformer is
to be asssuemed or known exactly.If the transformer is
already loaded you can kow the running PF by PF meter
connected.IF the PF is say 0.7 & you want to improve to
unity.You must add a capacitor of Total load in KW multiply
by a factor of 1.02.That is the value of Capacitor in KVAR.
Formula is PF (cos0)=0.7 Tan01=0.963
improve PF(Cos0)=1 Tan02=0
KVAR Required= P(Tan01-Tan02)=P(0.963).
This shall be devided in to number of stages as required.
Is This Answer Correct ? | 9 Yes | 5 No |
Post New Answer View All Answers
On what basis do you decide the ONAN (Oil Natural air natural) or Dry type transformer for a project?
HOW CAN I GET 5CORE HO7 CABLE SIZE IF I HAVE 1800A?
why T/F winding temp measurement cts are odd secondary current ie,109A/1.2A/1.4A?
Actually I have a doubt on neutral and earth.we use Ac power without taking neutral by connecting to earth,but at that time does it affects on efficiency of any electrical components or no? If yes how?
i want bhel placement paper for electrical if anybody having pl send to my id kavitha867@myway.com immediately
whit is 33kv power 300*300 cable full current with formula
Write down the brushes of a de machine.
WRITEDOWN FEW RELY CODES
Pl. share your experience about industrial-electronics repair of machine tool.
-What shall be short circuit current of LV switchgear for a 1000 kva, 11.415kv, 3 phase tranformer with 5% reactance.
What is vacuum circuit breaker.define with cause and where be use it device?
I am apply the AAI. So i want electrical sample question paper in technical with answer my id is vijayjobsmart@gmail.com
What is the Surge suppresor? Why using in a UDB's and How it works?
What is 11 N1 and 12 N2 in single phase Transformer ?
How can I model an open-delta ground transformer for a network supplied by 4 unit GTG and power transformer in ETAP?