What are the steps for Testing of 6.6KV HT Panels?
Answer Posted / rama raju (essar)
The following test are to be carried out for HT panels..
1) Functional test(In this test we can check control
wiring,power circuit wiring,Breaker Testing & loop test)
2) Relay Testing (all types of relays and power meters)
3) Meggering and hypertest.
4) polarity Test.
5) Primary Injection Testing.
6) Secondary injection Testing.
7) Breaker contactor resistance and timing.
8) MV Drop Test
9) Knee voltage Test depends upon CT.
10)Relay coil resistance & Pickup voltage and
Dropup voltage it depends upon ur relay.
11)IR value for surge Arrestor.
Is This Answer Correct ? | 51 Yes | 2 No |
Post New Answer View All Answers
what are the condition that makes hooter blow?
How do we calculate the Out put voltage of generator, after the excitation is being given?
what is the isolation transformer. what is the isolator?
What does the term “voltage regulation” means?
WHAT WOULD BE THE FORMULA OF WIRE GAUGE FOR A FULL LOAD CURRENT
What is stacking factor? What is its approximate value?
after how many spot we must chang secondry cable in portable spot welding gun?
Whether should be the oil level in OCTC transfomer? It should be upto winding immersed completely or should be upto tap changer s/w? How it will affect the performance of the transformer. Rating may be 33KVA
what will be the min and max voltage flow from neutral to earth?
Why an ac systems are preferred over dc systems?
how wecalculate breaking capcity of acb mcb mccb .explain with example
Mention the difference between Analogue and Digital circuit?
A 50Hz,4-pole,3-phase,star-connected synchronous motor has a synchronous reactance of 12ohmsper phase and negligible armature resistances.the excitation is such as to give an open-circuit voltage of 13.2kilovolt.the motor is connected to 115kilovolt, 50hertz supplying. what maximum load can be the motor torque,line current and power factor?
What is open loop and control loop systems?
how can i use REF and diffrencial relay both in 1 CT core for transformer protection?