What will be the full load current of 60KVA UPS. Suggest
for this formula.
Answer Posted / sujit288
60kva x 0.8=48kw or 48000watt
we know p=1.732xVIcos@
I=p/1.732xVcos@
I=48000/1.732 X 415v X 0.8(Where V=415v)
I=48000/575
I=83Amps
So Full load current is 83 Amps.
Is This Answer Correct ? | 71 Yes | 8 No |
Post New Answer View All Answers
if a.c supply is given to the motor,, what happen?
why do we lay up the core of a cable?
how desiel generate sart fail of eb?
i am going to give the JSEB,RANCHI exam for power plant,so i need some samples of papers related to that,so please send me these papers by my mail id.
What is the effect of atmospheric pressure & Temp; on efficiency of motor? Why NGR(Neutral Grounding Resistor) is used in 132/11 KV Transformer & how? What is the use of Auto T/F in Grid Station?
What is CCM in Electrical ? where can we use this material?
what is the basic construction diffrance between servo motor ans sqiralcage induction motor
WHY THE COLOR OF OUTDOOR TRANSFORMER IS BLUE ONLY???
What is the maximum and minimum rating of UPS?
there is an alternator 480 k.w, 400v,50hz, 4-wire running on load having leakage alternator body earthed current 38 A. is it within acceptable limit? if yes then give reference if no then how to bring within specified limit
what is POTT and PUTT explain?
At what speed 1 HP motor can run an electric car of weighing 400 kg?
What should be the length of transmission line so that we can see/obtain the full sine wave of voltage??
tell me about eletrical contractor
1) What are your personal strength? 2) What are your personal areas of improvement? 3) What are your expectations from from a particular job? 4) what are your carrier objectives?