what is the difference between earthed system and unearthed
system.. where do we use unearthed system because in
electrical catalogues always cable for earthed and unearthed
system is given..pls elaborate
Answer Posted / bikash chandra pal
WAHT IS EARTHED SYSTEM??
when the source(it may be feeding generator neutral point
or feeding transforme neutral or a bus through a zig-zag
transformer etc)neutral point of a perticular voltage level
of a system is earthed(may be solidly or through a
resistance/inductance), then that perticular voltage level
of the system is called as earthed system.
WAHT IS UNEARTHED SYSTEM??
When the above said neutral point is not earthed then that
perticular voltage level of the system is called as
unearthed system.
ADVANTAGES OF EARTHED SYSTEM
The system eathing(solidly or through a resistance or
impedance) is done to provide a returne path of earth fault
current, which in turne helps
1)To isolate the faulty part of the system due to earth
fault by sensing earth fault current.
2)To Reduce the insulation requirement of phase elements of
equipments connected in that voltage level & cost of the
equipment/s in turn. VIZ: Earthed grade cables are less
costlier than unearthed grade cables.
3)Fenomennon like ARCHING GROUND can be avoided.
So,
System with lesser Equipment cost(refer SL.NO.(2)above),
health of the concern part of the system(Refer sl no.(1) &
(3)above) remain protected.
DISADVANTAGES OF EARTHED SYSTEM
Possibility of interruption of power supply due to earth
fault,is more in EARTHED SYSTEM than UNEARTHED SYSTEM.
ADVANTAGES OF UNEARTHED SYSTEM
1)Possibility of continuation of power supply is more in
UNEARTHED SYSTEM, as tripping of system due to first earth
fault is not happens.
2)sensing of presence of earth fault through sensing of
concern system's neutral displacement is possible & planned
maintenance/earth fault clearence of the system is
possible,which supports better availity of the system &
lesser interruption of process.
DISADVANTAGES OF UNEARTHED SYSTEM
1)Isolation of the faulty part of the system due to earth
fault by sensing earth fault current is not possibele due
to first earth fault.
2)Insulation requirement of phase elements of equipments
connected is higher Hence cost of the equipment/s is
higher. VIZ: unearthed grade cables are costlier than
earthed grade cables.
3)Fenomennon like ARCHING GROUND is there.
So,
Capital investment is higher for unearthed System, But
availability of system is better.
Is This Answer Correct ? | 41 Yes | 1 No |
Post New Answer View All Answers
to hook up ten 50 amp rv pedastels at a lenth of 600 feet from the service what size will my service need to be and the size of wire will I have to run to each pedastel in series??????
Explain the following and how these are working with PLC Unit 1 I/O Module Card 2 Adaptor Card 3 Ribbon Adaptor 4 I/O bus 5 I/O Devices
CAN CU XLPE/PVC CABLE BE USED INPLACE OF LOW NOISE SCREENED CABLE? KINDLY GIVE REASONS
What are the main faults of DC generators?
How to calculate Grid rotor resistance(GRR) losses in slip ring induction motor?
What will be electrical cost per sqft for IT building (basebuild and fitout)and for residential township?
What will happen if i replace a inductive proximity switch with photo sensor in a machine?
TCS IS IT COMPANY THEN WHY DO THEY NEED ELECTRICAL &ELECTRONICS ENGINEERS?
How do we find the rating of a transformer, if it got burnt badly.
1) What are your personal strength? 2) What are your personal areas of improvement? 3) What are your expectations from from a particular job? 4) what are your carrier objectives?
What is the difference between rated and per unit in transformer?
An 8 pole, 50 Hz, 3-phase IM is loaded to a poing where pull out torque will occur. The rotor resistance per phase is 0.3 ohm and motor stalls at 650 rpm. The rotor reactance at stand still is A 2 ohm B 1.25 ohm C 3.15 ohm D 2.25 ohm
when we gave dc supply to 220v dc motor its rpm is 1200. then we gave 180v. how many rpm of its motor. gave answer with calculation at my ID.... ravizak@ymail.com
Why r u using pf panel. what the uses
if two transformers are placed parallel & both have fault impedance of 50KA will it increase or decrease show example?