Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the difference between earthed system and unearthed
system.. where do we use unearthed system because in
electrical catalogues always cable for earthed and unearthed
system is given..pls elaborate

Answer Posted / bikash chandra pal

WAHT IS EARTHED SYSTEM??

when the source(it may be feeding generator neutral point
or feeding transforme neutral or a bus through a zig-zag
transformer etc)neutral point of a perticular voltage level
of a system is earthed(may be solidly or through a
resistance/inductance), then that perticular voltage level
of the system is called as earthed system.

WAHT IS UNEARTHED SYSTEM??

When the above said neutral point is not earthed then that
perticular voltage level of the system is called as
unearthed system.

ADVANTAGES OF EARTHED SYSTEM

The system eathing(solidly or through a resistance or
impedance) is done to provide a returne path of earth fault
current, which in turne helps

1)To isolate the faulty part of the system due to earth
fault by sensing earth fault current.

2)To Reduce the insulation requirement of phase elements of
equipments connected in that voltage level & cost of the
equipment/s in turn. VIZ: Earthed grade cables are less
costlier than unearthed grade cables.

3)Fenomennon like ARCHING GROUND can be avoided.

So,
System with lesser Equipment cost(refer SL.NO.(2)above),
health of the concern part of the system(Refer sl no.(1) &
(3)above) remain protected.


DISADVANTAGES OF EARTHED SYSTEM

Possibility of interruption of power supply due to earth
fault,is more in EARTHED SYSTEM than UNEARTHED SYSTEM.

ADVANTAGES OF UNEARTHED SYSTEM

1)Possibility of continuation of power supply is more in
UNEARTHED SYSTEM, as tripping of system due to first earth
fault is not happens.

2)sensing of presence of earth fault through sensing of
concern system's neutral displacement is possible & planned
maintenance/earth fault clearence of the system is
possible,which supports better availity of the system &
lesser interruption of process.

DISADVANTAGES OF UNEARTHED SYSTEM

1)Isolation of the faulty part of the system due to earth
fault by sensing earth fault current is not possibele due
to first earth fault.

2)Insulation requirement of phase elements of equipments
connected is higher Hence cost of the equipment/s is
higher. VIZ: unearthed grade cables are costlier than
earthed grade cables.

3)Fenomennon like ARCHING GROUND is there.

So,
Capital investment is higher for unearthed System, But
availability of system is better.

Is This Answer Correct ?    41 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Is it advantages of having star-delta vfd than normal star vfd , if yes why?

2258


where the lexical paramater will use in fron end?

1867


In EHV transmission line a neutral grounding reactor is often placed at neutral point of shunt reactors. What is the recommended protection for this neutral grounding reactor? Should I use a fast closing switch to bypass neutral grounding reactor when this protection operates?

3234


What is the capacity of the Fastners 12mm?

2438


how to find motors H.P. whout any rating? (only give you a motor and multimeter)

6087


hi, i have 3x200KVA and 2 x 80KVA UPS with battery bank of 150AH 68Nos. and 100AH 204Nos., i need to install AC either ductable or PAC type, so can you help me to calculate heat load and capacity of the AC to install.

2722


What is the Nyquist criterion regarding control systems?

1089


What do you mean by cogeneration? What its working principle?

3206


CAN CU XLPE/PVC CABLE BE USED INPLACE OF LOW NOISE SCREENED CABLE? KINDLY GIVE REASONS

1877


what is vtg limit of earth and neutral at transformer side?

2035


What is inductance?

1193


Two bulbs of 100w and 40w respectively connected in series across a 230v supply which bulb will glow bright and why?

1057


How to findout raw or ups power? its not indicated in socket,

2041


8. A DYNAMOMETER TYPE WATTMETER RESPONDS TO THE.......

9286


Explain (in simple ) - root mean square. whats its role in electrical fundamandal.where its used

2394