What are the difference between C-Curve and D-Curve for
MCB's.
Answer Posted / bright spark
There is no A type.
B C and D types all consist of 2 similar parts:
The thermal trip, this is the same for all MCBs of the same
rating eg 6A.
The Magnetic trip, this is where the difference is.
B C and Ds have an increasing degree of initial "tolerance"
to overload.
B types have a limit of 3 - 5 times the rating.
e.g. a 6A MCB would trip with a surge of 18-30A.
C types have a limit of 5 - 10 times the rating.
e.g. a 6A MCB would trip with a surge of 30 - 60A.
D types have a limit of 10 - 20 times the rating.
e.g. a 6A MCB would trip with a surge of 60 - 120A.
Now you would think that the B curve would be the safest,
and it is, but not very tolerant of power surges. If you
have quite a few lights on in the house and switch on
another, this can be enough for that initial start up surge
to trip you whole lighting ring, and a reset at you consumer
unit. B types are notorious for this, but ideal for a ring
final where you don't have too many outlets, gives ideal
protection.
As you can see a type D 6A MCB can tolerate a 120A surge, so
a 32A Type D would tolerate an initial surge of 320 - 640A
before tripping!. Domestic Consumer Units will have a master
trip of @60 - 100A (80A is most common), hence why there is
never a need for type D in the domestic environment, not
unless you have a 3 phase incomer and have a car production
line in your back garden instead of a washing line!.
Is This Answer Correct ? | 205 Yes | 17 No |
Post New Answer View All Answers
DG cranking voltage?
why power factor is important?
what is draiv work
How can we calculate the KVA rating of a Distribution transformer from its core details?
what would happen if reactive power (kvar)is increased (more)or decreased (less)? how much exact reactive power should be maintained? and what should be done for that
what are the differences between 'exhaust fan', 'heavy-duty exhaust fan' & 'super heavy duty exhaust fan'. what are their power ratings ?
How to calculate the no of Ceiling fan (1200mm sweep) per unit area?
how u select control transformer for a mccb panels or any panels?for expample we hav 440 volts maim supply and control volts is 230v?
300m long and 30kw inductive loade 3phase supply how many size cable required
How to calculate KVA/VA rating of PT or CT from primary & secondary voltage or primary & secondary current?
what is cathodic protection and why it use in industries?
What is the universal motor?
How will polarity test of Dy5 Transformer ?
If any cable burnt how can we identify it burnt by high current of high voltage?
what is the voltage between earth to neutral in lift.