What core magnetic balance test of transformer?
How to do this test in a three phase Star delta (star-LV,
Delta-HV) transformer?
How to measure and where to measure?
thanks and regards
Austin
Answer Posted / mugaisi
Provide 2-phase supply on the HV side of transformer on two
phases.
Then measure magnetizing current in the supplied phases.
Then measure the voltages on the LV side.
Repeat the same for the other phases and measure current
and LV corresponding voltages.
The LV voltages should obey
ry = rb+by
and
rn = bn+yn
Is This Answer Correct ? | 39 Yes | 21 No |
Post New Answer View All Answers
circuit diagram of trip circuit supervision relay
Please tell me the earthing procedures adopted for the STAR-STAR 3 Phase transformer in india and give a better sugession for earthing
how is the cable tray designed & how its total length is calculated for an Industrial plant Say for Ex. (500KW Motor Load)
How to Prepare preventive maintenance shedule of machine tool.
3ph motor running with unequal kw and different pf what are the reasons
How to decide DO set rating of Transformer?
What is difference between insulating medium and fault current interruption medium in a switching device.
If a high resistance fault occurs,then what are the changes will happen in the system?
Two bulbs of 100w and 40w respectively connected in series across a 230v supply which bulb will glow bright and why?
can i connect wavetrap in 2 different phase in EHV line?
how does a shunt reactor maintains the bus voltage???
In Designing the rating & accessories of a MCCB how to choose the type of releases..means what is the basis for selecting, thermal magnetic, electromagnetic & microprocessr based releases
what is the difference between 4pole & 6pole DC Motors & give advantage ?
Pl. brief about break-down maintenance of machine tool.
Why we are going for converter transformers for DC drives application instead of distribution transformer?