I HAVE CONSUMER WHOSE POWER FACTOR IS 65% I WANT TO INCREASE
IT TO 98%.HOW TO CARRY OUT?
Answer Posted / navin
reqd KVAR = KW ( Tan (cos-1 P1) - Tan ( cos-1 P2) )
KW- Load KW
P1- Existing PF angle
P2- Desired PF angle
Is This Answer Correct ? | 5 Yes | 1 No |
Post New Answer View All Answers
why do you add the load short circuit impedance when considering short circuit amperage. It seems that you should only consider supply. If you need to consider loads and you don't know what loads are to be added , what would be a good sub-transient reactance rating for the loads?
why are the maintaine power factor and how can this control and this is how work.
What is ST and specify its range of voltage.
what is the minimum recommended leakage current of an earthed cable connected to the body or skid of an alternator
why swinburnes test cannot be performed on series machines?explain
Dear Mr B C pal...Can you plz. put some light on principle of operation of Z-Ct in conjunction to its use with 1Cx1000Sqmm HT Cables & Directional Ground Fault / Over Voltage Relays...Regd..Parag v K 9899115632
Whether should be the oil level in OCTC transfomer? It should be upto winding immersed completely or should be upto tap changer s/w? How it will affect the performance of the transformer. Rating may be 33KVA
what should be correct gas pressures to be a 1.5 ac unite
Why IR value of the (HT cable Plus synchronous motor) is less while individually having IR values in GΩ?
how to decide no of electrodes for 1600A LT Main incomer panel
what will happen if synchronous machine rotor fed from single phase ac supply
what are the protecyion of transformer & generators
What is icu and ics in Acb and how many time icu or ics passes from breaker?
10 tube light connect in mcb breaker.one tube light is fault.so breaker is tribe.how fault is rectified.(using 3wire phase,earth,neutral)
Dear sir, How to calculate 3.5 core pvc aluminium armoured cable meter wise carrying amps rating.Please give the solution with a good example.