how to test generator protection rotor earth fault relay
and locked rotor test?

Answer Posted / gajanan koshatwar

generator earth fault relay basically monitors the
insulation level of roror winding and shaft ground. The
rotor earth fault relay injects the low frequency pulse in
one field winding terminal wrt ground and in turn it
measures the value of refelcted pulse and claculates the
insulation value.

For testing generator earth fault relay put specific values
of precision resistors across terminals and observe the
values in relay if display is provided, or set the trip
value less than the resistace put for testing , then relay
will issue trip command and this proves relay is heathy.

Gajanan koshatwar manager Power plant

Is This Answer Correct ?    41 Yes 6 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

induction 3 phase motor terminal connection

2058


what type of earthing do for dry fissure rock?

2042


What is milivolt dop test in Busducts? What is its significance & procedure to do the test?

1587


What is use of starter and choke in tube light

1304


. What is Electrical Life & Mechanical Life of Circuit Breaker? 2. What is Electrial Life & Mechanical Life of Magnetic Contactor? 3. What is RCD, RCCB & RCBO? 4. What is the Between defferance of RCD, RCCB & RCBO?

2836






Can we use BS 6651 and BS EN 62305 standards for computer room lightning ptotection in substation?

1752


hi friends how 3 phase converter functioning ?what is working principle of rotory phase converter ?

1628


how to select correct size of power cable for inverter duty motor

926


What is depreciation factor?

1773


full form of electrical?

2296


why we can stote dc? why we cant store ac?

1625


What size cable (based on voltage drop) is required to supply a 40 A three phase boiler if the wiring system is 75V single insulated cables installed in non-metallic rigid conduit 56m from the main switchboard? Voltage drop in the consumer's mains is 8V.

1489


one conductor length is L.and i am strech uniformly this conductor and made length is 2L.so resistance of this strech conductor is R=4R..but i want to know about area of stech conductor hows it become a/2..

1688


How to select the cable and voltage drop in circuit?

1189


As we know diode work on both negative and positive but converting ac into DC we have to given a/c from negative of diode or positive side.please give me answer.

1172