how set earth fault over current in relay
Answer Posted / kiran sule
In any relay Set earth fault to minimum That means If Earth
fault range is 20 to 80 % of secondary current then set it
to 20% . In case of over current calculate rated current
and add 5%for relay & ct error and 5% to over load that
means set it to 110% to full load capacity.
If for 200/1 CT If full load current is 160 that mens 80%
to secondary current of Ct+10% relay CT error and Over load
that means relay ia seted to 180A interms of secondary at
0.9 a that means 90%
Is This Answer Correct ? | 19 Yes | 2 No |
Post New Answer View All Answers
where can the transformer having vector group Yny0 be used??
how the B-H loop obtain under the static condition
What is meant by RVT and NDR ? expansion and details of it
i completed my DEEE. and i want to electrical c license. how to get it..?
I have 1500/1A CT If i connect this CT in 6.6KV bus bar means what will be the voltage present in CT?
When are the directional relays used?
what is the synchronous timer ? and it applications.
how to calculate magnetic force genrated by a coil ?
if main CT is of ratio 50/5, and meter CT is -/5 what will be overall multiplying factor of meter.PT is 11000/110 .
How to address the servo drive for motor
what are the usual topology of transformers at different substations in the power system and why that particular topology is choosen. what are the limitaions of that topology?
WHAT SHOULD BE THE BEST CURRENT RATINGS (PRIMARY / SECONDARY)FOR A CT INSTALLED AT THE INCOMING 11KV PANE? WILL IT BE CALCULATED ON THE BASES OF MAXIMUM DEMANT VALUE OR ON SUM OF ALL TRANSFORMER'S KVA? NOMALLY MAX DEMAND REPRESENT THE MAXIMUM OPERATING LOAD OF THE PLANT AND TOTAL KVA OF (SAY 5 NUMBERS TRANSFORMERS) REPRESENT THE CONNECTED LOAD. WHICH i.e. MAX DEMAND KVA OR CONNECTED KVA ARE BETTER TO USE FOR CT CURRENT CALCULATION? PLEASE ANSWER.
How can a equal potential zone be carried out in conductors?
What is formula calculation size cable wire ?
what is the difference between directional & non directional earth fault with example please explain.