Answer Posted / raffi
Calibration procedure:
calibration equipment: calibrator with handpump
For ex: Range of Transmitter is 0-100psi
Step1: connect the calibrator to the transmitter
Step2: connect the multimeter in series with transmitter to
verify the transmitter o/p in mA
step2: Apply the pressure to the transmitter by hand pump
in calibrator
Step3: compare whether both calibrator and the transmitter
showing the same value.if you applied 50 psi throuhg the
calibrator then the transmitter should have to show the
same value.If you find any error.Do the zero/span
Adjustment.by adjusting the zero/span screw
increasing/decreasing
step4: compare the transmitter and calibrator as per follows
calibrator Transmitter Transmitter o/p
in psi in psi in mA
0 0 4
25 25 8
50 50 12
75 75 16
100 100 20
Is This Answer Correct ? | 22 Yes | 0 No |
Post New Answer View All Answers
what is piezoelectric transducer?give an example in power plant n state its principle?
control panel design guidelines
what is the reset offset and control system in instrumentation
How many types of sensor
what is exact time to study dcs and plc cources
how to calibrate mass flow meter (Coriolis)? Example calibration range: 0 to 2500 kg/hr line size 3" fluid: Etheline glycol (MEG)
Explain the combusion chamber
How to Calibrate Flammable gas detector in field
all types instrumentation questions want
please send me some question papers of HPCL aptitude test ?? please send it to bipinb.28@gmail.com ...
what is IEC code in cables & how to selecting cables?
Can anybody tell me how to select the size of earthing cable for DCS & PLC system.Please tell me any relevant answer here or mail it to me.
What are different types of valves?
How can a d.p. Transmitter be calibrated?
what would be the minimum flow rate that we can measure on rotameter..?