Answer Posted / raffi
Calibration procedure:
calibration equipment: calibrator with handpump
For ex: Range of Transmitter is 0-100psi
Step1: connect the calibrator to the transmitter
Step2: connect the multimeter in series with transmitter to
verify the transmitter o/p in mA
step2: Apply the pressure to the transmitter by hand pump
in calibrator
Step3: compare whether both calibrator and the transmitter
showing the same value.if you applied 50 psi throuhg the
calibrator then the transmitter should have to show the
same value.If you find any error.Do the zero/span
Adjustment.by adjusting the zero/span screw
increasing/decreasing
step4: compare the transmitter and calibrator as per follows
calibrator Transmitter Transmitter o/p
in psi in psi in mA
0 0 4
25 25 8
50 50 12
75 75 16
100 100 20
| Is This Answer Correct ? | 22 Yes | 0 No |
Post New Answer View All Answers
what is temperature compensation?
What is sensitivity in vibration probes..?
What is Alpha & Beta fctors related to Orifice Plate & its relation with flow?
if in a level tx height is given, how u calculate the ranges of the tx?
what is actual drum level and compensated drum level?
dear friends, i have seen flow as the selection critriea in presure guage (bourdon tube) and i would like to know what is the relation between flow and performance of pressure guage other parameters i found in the data sheet are pressure max. 1ksc temperature max. - 50 deg c line size - 80NB operating range - 1ksc pr. guage range - 0-2 ksc thank u,
when placing a vent or drain hole on an orifice plate should you measure from the center of the bore up or down for the vent placement?
What is the constant voltage unit?
i am preparing for BARC ,so plz mail me how to prepare for BARC. ALSO IF POSIBLE SOME RELATED QUESTIONS. MY MAIL ID IS khushi_4uall2003@yahoo.co.in
Why use ball valves on Gas pipelines instead of gate & or globe valves...means basic diffrence or use of these valves..how designers knows this type of valve with rating is required...
Explain working principle of lvdt?
how to calibrate mass flow meter (Coriolis)? Example calibration range: 0 to 2500 kg/hr line size 3" fluid: Etheline glycol (MEG)
what is isloted barrier how it works and what are the main purpose.how it make safe area.
1.can you use SCADA instead of DCS,DCS instead SCADA 2.Difference between DCS and PLC,can their role be reversed i.e. role interchange 3.Difference between RTU and PLC
Actual using of tube bender to bend 2 opposite 90 deg at correct measurement center to center of tubing.