What core magnetic balance test of transformer?
How to do this test in a three phase Star delta (star-LV,
Delta-HV) transformer?
How to measure and where to measure?

thanks and regards
Austin

Answer Posted / e.saravanan

MAGNETIC BALANCE TEST

THIS TEST IS SIMILAR AS OPEN CIRCUIT TEST

PROVIDE THE SINGLE PHASE SUPPLY (BELOW 230 V)TO THE STAR
SIDE OF THE TRANSFORMER BY PROPERLY CONNECTED

1.GIVE SUPPLY TO 2N AND 2U AND THEN MEASURE THE VOLTAGE ON
2N2V AND 2N2W
(i.e)IT SATISFIED THE CONDITION

2U2N=2V2N+2W2N

SIMILARILY THE TEST CONDUCTED ON OTHER TWO PHASES BY SAME
MEANS

(NOTE: NO ONE SHOULD BE STAND ON HIGH VOLTAGE SIDE WHILE
TESTING )

Is This Answer Correct ?    100 Yes 32 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

For a three phase induction motor, what will be the effect on motor if the neutral of the system is shifted to say 20 deg.?

1402


In AC if the direction of current keeps reversing every half cycle, how does it propogate through the transmission lines?

1643


What is the effect of pd controller on system performance?

643


1.Z transform always lies around ? a) origin b) pole c) zero d) z=1. Multiples Mcqs which is bother me can’t find answers on internet. Some help required with little explanation . Note: this is not homework or related to any test. Thanks

1938


if we have a industrial load of 400 kilowatts with 415 volt AC then how much total harmonic distortion (thd%) should be acceptable for steady power system.

1573






A 10 MVA, 66KV, 50Hz, Y-connected 3-phase alternator has synchronous reactance of 0.635 Ù. It is working at full load at 0.8 lagging p.f. condition. Find torque angle, neglect armature resistance.

2078


How does HT work & Voltage required?

1744


electromechanical relay type identification example : type=tjmh t-stants for j- m- h-

1953


how to find the capacitance value of the motor while running??

1400


HOW TO CALCULATE THE VT SIZING?

2443


What is pd controller?

645


bitumar

1802


Dear all: Recently we got a question about Interface between PMS and SAP-PM.once we got a update message from PMS.we should set the deletional flag for functional location in SAP system.Is there any FM or BAPI to use?There are only functional location create and change provided by SAP. Best regards!

1587


how does directional relay work incase of ac ?

1023


why the voltage and current in a long transmission line are called travelling wave?

1782