RATING OF LIGHTENING ARRESTER FOR 11 KV LINE IS 9 KV BUT WE
KNOW THAT LIGHTENING ARRESTER IS USED FOR OVER VOLTAGE
PROTECTION SO WHY NOT THE RATING OF LIGHTENING ARRESTER BE
MORE THAN 11KV ???????????????//
Answer Posted / elangovan t
Lightning arrester is to protect the system from any high
voltages such as lightning.
If the system voltage is 11kv, then the phase voltage will
be 11/sqrt(3)=6.35kv. It means the RMS voltage of the phase.
The maximum voltage or the peak voltage across the arrester
and earth will be 6.35*sqrt(2)=8.98kv.i.e 9kv.
Therefore, for 11kv line it is rated for 9kv.
Is This Answer Correct ? | 135 Yes | 10 No |
Post New Answer View All Answers
3phase motor can be used as a Prime mover for alternator.
what is the id1 & id2 setting in differential protection relay of CSPC?
how to find out cable size if load is 2800 watts, 230 volts AC supply and load distance is 1800 meters
how power is generated,and transmitted to our home..pls explain briefly in simple words.
how to calculate sizing of NGTR (Transformer rating,Loading resistor value and Current rating of resistor) and what is the X/R ratio. Details : 11kV,Capacitance 1.73532 micro farads,40kA for 1sec.
grr resistance & contrator malt continuous
What is meant by turbo alternators?
WHAT IS DEAD END IN PROTECTION?
how external lighting design? please give examples?
Can anyone please give me the parameters , formula needed to calculate the circuit breakers for building services.Thanks
1.What is the range of stator resistance of 3-phase induction motor? 2.Two electrically operated vibro motors are foxed in parallel direction in vibrating feeders. what is the direction of both vibro motors?
What are the protection required for Transformer, motor, Line, Generator, capacitor, that all i have to refer which standard?(Like Transformer detail IS 2026)
what is the correct method for the outdoor termination of 19/33 KV HT cable step by step?
how we calculate the dick for a pole?
what is the concept of directional power?