Answer Posted / harsh zala
Yes, We can use control valve without a positioner. The
basic purpose of positioner is to supply required punemetic
air w.r.t 4-20 mA standard signal, you can say for example
3.2 kg/cm2 to 4 kg/cm2. and it also checks for the
appropriate vavle opening(feedback) and stops air supply
going to valve actuator.
Without Positiner we can use control valve,but we must have
i/p converter, which generally converts 4-20 mA signal to
0.2 -1 kg/cm2, so in that case valve will not opearate
fully . but it will opearate upto certain level.
So when positoner got fail and we dont have new one, and if
we require valve to be controlled upto certain level, we
can use i/p converter,
Is This Answer Correct ? | 20 Yes | 6 No |
Post New Answer View All Answers
what is a vortex flow meter,mass flow meter and electromagnetic flow meter.particular use of this.means in which condition particular meter is used.
hii my name is sujith...i am preparing for HPVL GET 2010... so ,,,pls help me by send any previous questions or material to my site.....(Msujith_12@in.com) thank q
Programmable Logic control.
Difference between dcs and plc including date processing and architecture.
Speedtronic system .
What is the diffrence between digital signal processing and discrete signal processing?
Why upper weighing limit of electronics balance is 90% of the total weighing capacity?
Actual using of tube bender to bend 2 opposite 90 deg at correct measurement center to center of tubing.
What are the type of bonnets in the control valves?
What is difference between Ionization heat and bimetallic heat
why I need valve guard and whats different between guard and positioner ??
principle of dead weight tester ?
what is the difference between attemperator and desuperheater ?
In VVVF DRIVES VOLTAGE IS ALSO VARY WITH THE FREQUENCY. HOW? WHAT IS THE DIRECT FORMULA RELATING THESE TWO.
What is difference between radial vibration and axial vibration explain in detail .