If the capacitor bank is installed in switchyard say
132/22kv then on LT side say 22kv/0.433kv is it necessary to
install capacitor bank for maintaining power factor. if pf
is maintained on HT side then will that be maintained on LT
side as well.if not then how&why??????/ please
explain...........
Answer Posted / zahid noor
If capacitor bank is installed in switchyard & capacitors
are connected on HT side , it will try to balance losses of
transmission line and not towards LT side, where as for
maintaining /increasing LT side voltage, we need to install
seperate capacitors nearer to load so as to maintain PF at
LT side also depending upon connected load & distance of
equipment connected in LT side.
Is This Answer Correct ? | 12 Yes | 0 No |
Post New Answer View All Answers
Explain the laying procedure and laying depth of submarine/subsea power cable for 220/400KV system? Also available cable diameter?
Why choke coil is connected in series with starter in tubelight??why starter is connected in parallel to tubelight??
In ACS 1000 drive we are using 12 pulse converter,why don't use 3 pulse converter.
Discuss about gear cutting machines.
Dear sir, I completed DECE In the year 1995.Now i am working in a private company from last 10 years as an Electrical supervisor.The company having a 1000 KVA transformer.Now i try to apply "C" Licence. I am eligible or not.If not eligible,pls give solution.
What is the end effect of linear induction motor ??
sir my exam is on 19/6/2013 under electrical branch pls send me sample aptitude questions as well as sample technical questions for jindal steel and power company
Name of the relay of low lub oil presuure in DG sets
Sir pl provide 5 year sample paper for post junior engineer(electrical).I have currently applied for junior engineer (electrical) on RRB Ajmer
A 3-PHASE TRANSFORMER IS USED TO STEP-DOWN THE VOLTAGE OF A 3-PHASE, 11KV FEEDER LINE. PER-PHASE TURNS RATIO IS 12.FOR A PRIMARY LINE CURRENT OF 20A, CALCULATE THE SECOUNDRY LINE VOLTAGE, LINE CURRENT AND OUTPUT KVA FOR FOLLOWING.A)STAR- DELTA.B)DELTA-DELTA.
3ph motor running with unequal kw and different pf what are the reasons
Why reactors use before incoming of ac vvfd drive?
what about GD square and its important for motor design?
what is the use of the circle diagram
Write down the design procedure of commutaj.