Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

why is the vector group analysis done in transformer tests

Answer Posted / joe callaghan

Transformer vector relationship is tested by shorting the
primary A phase to secondary A phase, then applyying a
three phase voltage to the primary side of the transformer.
Voltage measurements are then taken as follows:

A-B
B-C
C-A
B-b
C-b
B-c
C-c

These values will then allow you to draw the vector diagram
of the transformer.

Is This Answer Correct ?    32 Yes 9 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what about GD square and its important for motor design?

3843


How to calculate per unit impedance of transformer?

2218


How to arrange a hous hold earthing system to keep minimum earth resistance( below 7ohms).

2188


Pl. give me checklist for installation & commissioning of machine tool.

2317


What is cable tray, its type, and its support?

1161


When will you multiply and devide with derating factors to the actual value while sizing the cable?

1957


I just purchased a 4 position cam switch to be used to operate a 3-speed blower motor. The motor is a 10 amp motor and has 3 wires that are used to control speed. The cam switch was rated at 660V 20 amps but when I received it, I noticed that it has AC-15 operational current rating (Ie) of 4/5 amps. If I am reading the label correctly. the 4/5 amps is related to 440v/220V (Ue). Other ratings are AC-3: 5.5A, AC2: 7.5A and AC-4: 1.5A. My questions are 1) Is it safe to use this switch with the motor I have 2) what is the difference between the 20 amp Ith ratting and the Ie operational ratings?

1760


Why back emf used for a dc motor? Highlight its significance.

1205


what is formula to cal cute earth pit numbers and size of earth strip used in earthing?

2226


what happen if the supply is given to the stator of the 3phase induction motor with out assembling the rotor ?

1927


what do u understand about FACTS? how they are useful?

2005


What are the two basic types of transformers?

1183


working of diesel generator ?

1850


how to calculate the battery AH

2767


how to Select its CORE in electrical cables based on its applications? or Application of various types of electrical cable based on it CORE?

3267