what is diffrence between analog card and digital card in
plc.how analog card work,Please explain in detail.Please
send it on abhi_vyas@sify.com
Answer Posted / kulamani meher
digital card used for digital input and digital o/p.digital
i/p means status of allswitches whether it is on or off and
pump rts (ready to start),run conform & trip
indication .digital o/p means pump start ,stop,
local/remote. it deals only binary either on or off (0 or
1).analog card deals with analog i/p & analog o/p means 4to
20 ma.analog i/p means for ex. in case of control valve %
of open & close needed so according to 4 to 20 means 0 to
100% open close .analog o/p means o/p from all
transmiter.for ex . in case of level transmiter 50% level
in tank means o/p is 12ma .4ma-0,8ma-25%,12ma-50%,16ma-
75%,20ma -100%.
Is This Answer Correct ? | 22 Yes | 6 No |
Post New Answer View All Answers
What is the advantage of using locally fabricated hook ups over Pre fabricated hook ups in process instrumentation?
defination of radial vibration?
What are continuances of connecting earthing and shield of branch cables (instrument to Junction box), at the same earthing pot provided on JB? Is it ok, or may produce some problem?
describe flow nozzel principle?
what is difference between HOT permit and cold permit
how to calibrate 0- 150 psi presure gauge by dead weght tester
Actual using of tube bender to bend 2 opposite 90 deg at correct measurement center to center of tubing.
How d.p. Transmitter can be applied to open tank?
model question paper of instrumentation for Jindal GET 2010.plz reply sudhanshukumar08@yahoo.com
In turbine, what does term CDP, NI, NH, HSSOC, means
How flow can be measured with dp?
What is zener diode? What is voltage regulator?
what does the ratio 800-400-300-200/1-1-1-1-1 in the specification of current transformer indicates?
We Have Two Field bus Pressure Transmitters of Different Sensor Range (I.E One is of Lower range and Another is of Higher Range).Is same Process Line. My Question is Can i provide Saturation Limit to my field Bus Transmitter as We can provide Saturation current limit to HART Instruments. As During Low Pressure Both Working OK ,But During High Pressure, transmitter with Lower sensor range Goes to Fault mode as Beyond its Sensor Limit it can Measure, So may I provide Saturation point Some where to Suppress This Fault during High Pressure.
what is the field bus calble ? what are diffrences in orang colur cable and black coular calble ?