What is the role of link in neutral in a three phase ac
system?
Answer Posted / nbsubrahmanyam
In 3phase ac system ,In the case of link in neutral, we
should not use fuse.
(neutral is using at distribution level for getting single
phase or 3 phase 3wire 4wire system to supply the power to
the some loads),
Suppose we use the fuse in the neutral line,if any fault
or break occur in the neutral line, but current flows from
phase/line to load and come to neutral wire where it has
break,there will be a chance to shock to human
beings/workers who will do the works regarding the repairs.
we generally putting fuse in phase/line for protecting
the equipment/device from high voltages/currents.if any
fault occur in the phase/line ,current will not flows from
fuse,only it will come fuse hence there is no problem. but
in the case of neutral, the current flows through out
equipment that may lead to creat some problms as mentioned
above.
that's why we w should put only link for neutral in three
phase ac system.
| Is This Answer Correct ? | 22 Yes | 4 No |
Post New Answer View All Answers
what are the components in electrical control panel (for example: 415V, 3-ph, panel to operate utility and 3-ph DG set).
what is the advantages of having in-built acvvvf (without seperate inverter in the control panel)in the drive system of elevators?
WHAT IS DIFFERENCE BETWEEN MANUAL CONTROL AND MAGNETIC CONTROL AND STATE ITS ADVANTAGE /DISADVANTAGE
dear all i am kumara now current working in electrical designing of control and relay panel i want learn some substaion design then any book are available. pls mention name and authour
What will be advantage if we put some load in neutral of grounded star transformer & loadshortcircuit current,rated current of cable & MCB with example?
i have 500 amp inductive load of motors ,,,pleas tell me how can i calculate for capacitor bank for improving my power factor to 99 .....calcullations for capacitor bank,,,,
what is the minimum pay scale for electrical engineer (building construction)in kuwait? plz revert back with yrs of experience & pay scale respectively.
stand by earth fault protection (51G) for transformer rating 2000 kVA,Dyn11,33/0.400 V. LV NCT ratio and necessary resistor and metrosil values how to calculate
is there any role of power factor with frequency variation? and how we can manage the frequency variation?
What is meaning of out of phase (making & breaking) capacity And how to calculate
sir pls tell me . our ct specifications are 120/5 ,2 core , 0.2 and 5p10 class , 30va and 30va buden. insted of 30 va i want use 15 va. can i use?
What is the phase relationship between the primary and secondary voltages of a transformer?
what is meant by IGBT how they differ from tyristor ?
How to measure the earth resistance value in a concrete pavement(flood light area)?
why various test are performed on electrical panels & power cables before commissioning on site & what are these test???