Procedure for conduting vector group test on power
transformers.why it is conducted?
Answer Posted / maheshreddy
Purpose: The Polarity and Phase relation tests are
importent when two or more transformer are to be
paralleled.Parelleled transformer must have the same
polarity and phase relation to avoid parial or complete
short circuits.
Test Procedure:(Yyn11)
The L.V. vector will be superimposed on H.V. by connecting
1U & 2U Terminals. The three-phase voltage will be applied
to the line terminals of H.V. winding. Voltage measurement
will be done across:
1U-1V:
1V-1W:
1W-1U:
1V-2V: 1V-2W:
1W-2V: 1W-2W:
1U-2N: 1V-2N:
Checks: - 1V-2V = 1V-2W
1W-2V > 1W-2W
1U-2N + 1V-2N = 1U-1V
| Is This Answer Correct ? | 41 Yes | 14 No |
Post New Answer View All Answers
what is the mechanical safety of DG ?
I NEED RRB APTITUDE QUESTIONS AND MODEL PAPER,PLEASE SEND MY E-MAIL joo28_eee@yahoo.co.in
Can 4pole (3 phase+neautral )RCCB proper functioning in only 3 phase load (no neautral, no Earth) ?
how to calculate fault level?
briefly explain the main blocks found in a microprocessor based system
what will be d.g. capacity to cater together for 14hp A.C. load & 3kw lighting load
Why reactors use before incoming of ac vvfd drive?
How npn and pnp transistor works
how to do the ductor test?
hey guys help me out.....what are the industrial uses/functions of nozzles in industries
How to select a contactor? How many types of contactors are available
EXPLAIN WHY THE SURGE CURRENT RATING OF AN MCCB OR CIRCUIT BREAKER DECREASES WITH INCREASE IN THE RATING OF MCCB OR CIRCUIT BREAKER.
how to introduce yourself
in dc series motor if field wdg is shorted then
What Is Connection APFC Panel In Compony.