We know that, in case if there is a faulty insulation,or
sc, the current is bypassed to earth through the earth wire
that has low resistance.Actually, what will happen to that
current that flows through gnd?In that case,if we come in
contact with that faulty appliance, wont that current flow
through us as we form a closed path by standing in gnd?Is
grounding a safety measure?
Answer Posted / debasis
Q. 1> Without a close loop ckt., no current flow.
It should be a close loop path.
Example: If earth fault occured in your home, then current
flowing through earth to transformer neutral(star) point as
the star point of a transformer is grounded.
Q. 2> If you touch the above faulty appliance, idealy,
there should be no effect. But practically, A small current
will flow through body because ur body resistance is in the
range of few kilo to mega ohm. But nothing to be serious.
Thats why we provide earthing.
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
how is capacitor bank look like
How do we arrive at selecting reactive capacitance value as 30% of h.p rating of motor?
My question is whether bellow formula is correct to find bus size for 46kA for 0.5 second & what is RT in bellow formula. formula to calculate the size of busbar to withstand the thermal stresses due to currents with duration of 0.2 sec to 5 sec. Sp = RT( I x I x t) / K Where Sp – is the cross sectional area of bus bar in millimeters. I - is the value of AC fault current. t - is the operating time of disconnecting device in seconds. K – is the factor depending on the material of the conductor, insulation and initial and final temperature. Value of ‘k’ for copper is 143.
What are the main faults of DC generators?
What is voltage ratio of a transformer?
what is distribution board?
excitation limit of an excitor
in a simple IDMT relay we use neutral point of ct for earth fault then what is the requirement of neutral ct and cbct?
What kinds of decision are made about CT from it's Knee point(voltage & current)?
I have 2500KVA transformer delta/star,13.8KV/380V provided with LV 4000A breaker. Already I have 2300KW motor feeder with a full load 90%. Is it possible to connect another 1600A from that breaker? If so how the calculation is done?
What the main causes of transient interruptions on Over-Head Distribution Lines?
what is the necessity of under ground cables ??
How to address the servo drive for motor
how is the magnetic current test is different in delta-star and delta delta transformer.
substation+ plc system