Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

why in three phase 440 circuit in all phase current is
almost equal L1-35 A,L2-34 A ,L3-31 A but in nutral when i
check with clamp meter it shows 25 A?

Answer Posted / kiran

Principle is vector summation.
Ir + Iy + Ib = 0

and not arithmatic summation.

Since neutral current is substantial 25A, the three RYB
vectors are not 120 degree apart. Means powewr factor in
each phase differs drastically. Thats why though there is
no much difference in RYB current, neutral has substantial
current.

Is This Answer Correct ?    18 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

A 7 storey building has a floor area of 35,000sq.ft on each storey. On the ground floor 11KV electrical sub-station is to be erected. A load of 3kw for every 400sq.ft (p.f is 0.8) is proposed for each floor. fire pump 7.5hp, water pump 5hp, lift 2 nos, each 10hp and 20shop load of each shop is 5kw. calculate a. load each floor b. total load of building c. L.T feeders for aech floor and from transformer to main. d. distribution diagram e. capacity of sub-station/capacitor bank f. line diagram

2769


11kv/433v delta/star distribution transformer primary side full load Ht current is 83.33A in , but input side VCB rating 800A.why?

1610


in my industry we are using 3 step up transformers for induction heaters..i.e 415/580v and other are 11/440v.in power consumption does a step trnsformer makes any difference compared to step up?? plz explain

1804


in dc series motor if field wdg is shorted then

1803


how to calculate the lightning arrester conductor @ no of earth pits required

2057


How should i design a 1ph & 3 ph transformer. Kindly let meknow all steps and formulaes related to design from scratch.

1946


How to calculate the heat load for a electrical room

3019


Why 30kw 40 hp 4 pole 3ph induction motor over heated?any steps on reduction in heat?

1616


what is draiv work

1839


how can we select the type of wire.what factors we have to look on it , do we have some formula to calculate it. please guide me on it

1897


Explain M Var? Which types of problem occurs when reactive power increase at the time of full load of plant and at the time of synchronize of plant?

1728


explain wiring system

2512


how to find 5 kilo meter long under ground 33 kv cable fault location if IR VALUE shows 0.05 M ohm @5000 volt.and cable fault locator shows some time fault distance 3 kilo meter ,3.7 kilo meter and some time 1 kilo meter? now how to find the fault location that where is leakage. note--it is tested with 5000 kv megger and insulation resistance is 0.05 M ohm. and some time 0.03 M ohm comes.

2153


show the single line diagram of star delta starter with single phase preventer

4577


How do you determine the size of transformer radiators in a transformer?

1880