why in three phase 440 circuit in all phase current is
almost equal L1-35 A,L2-34 A ,L3-31 A but in nutral when i
check with clamp meter it shows 25 A?
Answer Posted / kiran
Principle is vector summation.
Ir + Iy + Ib = 0
and not arithmatic summation.
Since neutral current is substantial 25A, the three RYB
vectors are not 120 degree apart. Means powewr factor in
each phase differs drastically. Thats why though there is
no much difference in RYB current, neutral has substantial
current.
| Is This Answer Correct ? | 18 Yes | 2 No |
Post New Answer View All Answers
explain single phase series motor
how to apply b license to c license in tneb
we have one oven for 12 zone we are installed ir lamp in oven we control load from thyrister and 0 to 5vdc so our zone no 8 getting bright in fraction of second so what we do.. Please answer
Why space heater is required for each verical bus bar chamber? if one space heater is adequate or not for anti condensation?
What is the type of earth fault protection used in battery? explain.
What are the symptoms of a bad PG card of a drive (inverter) esp. of Yaskawa Ac Drives (inverters) G7 ?
What is vaccum currcuit breaker.define with cause and where be use it device?
Why we specify TNC switch with 1NO 1NC ,2NO 2NC ? how we get connection.?
I need a formula to calculate the size of cable as per load but in the terms of length. Please Reply me as i search lot of sites but i did not get the answer.
Is Transol transformer oil comparable to nynas nytro libra?
comparision between ACB and VCB
What is the classification of hydro projects based on installed capacity?
What is effect on in zone and out zone fault if CT chosen for phase side is Vk/2<5mA and Neutral side is Vk/2<15mA on REF protection of Transformer
Can you any one explain application of buccholz relay operation and pressure relif device operation of power transformer
What is the difference between isolators and electrical circuit breakers? What is bus-bar?