why in three phase 440 circuit in all phase current is
almost equal L1-35 A,L2-34 A ,L3-31 A but in nutral when i
check with clamp meter it shows 25 A?

Answer Posted / kiran

Principle is vector summation.
Ir + Iy + Ib = 0

and not arithmatic summation.

Since neutral current is substantial 25A, the three RYB
vectors are not 120 degree apart. Means powewr factor in
each phase differs drastically. Thats why though there is
no much difference in RYB current, neutral has substantial
current.

Is This Answer Correct ?    18 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the function of the generator exciter?

916


is there any lightning by passer is arranged in ship like buildings?

1464


what is the purpose of silicon dropper used in battery charger?

6643


how to measure the transformer resistance values(dyn11)?and howmuch the minimum value?

1653


completed BE & done apprentice at tneb & having experience 6 years. want to get c license. will apprentiship & BE be helpful for getting c license. will i get any preference by showing this?

1186






WHY THREE PHESE SYSTEM VOLTAGE APPLIED IN 440 VOLT

1913


what will happen if synchronous machine rotor fed from single phase ac supply 

1295


low frequency protection why recomend?

1807


hi everybody how to design string combiner box (scb) internal parameters like bus bar and spd (surge protection device and fuse which place to set that,and also bus bar one particular cross sectional how much heat generated and how much power loss tell me Clearly and briefly

1532


what is a synchronizing lamp ?

980


How is operate breaker failure scheme in substation

1528


why occ characteristics curve in not tracing back when we are bringing back the rhoestat?

1426


Can any body tell me the different types of LT cables & their application.

1618


is it possible to turn on the single phase star delta on delay timer using 24 v dc ?

1463


application s to shunt coil

1493