why in three phase 440 circuit in all phase current is
almost equal L1-35 A,L2-34 A ,L3-31 A but in nutral when i
check with clamp meter it shows 25 A?
Answer Posted / kiran
Principle is vector summation.
Ir + Iy + Ib = 0
and not arithmatic summation.
Since neutral current is substantial 25A, the three RYB
vectors are not 120 degree apart. Means powewr factor in
each phase differs drastically. Thats why though there is
no much difference in RYB current, neutral has substantial
current.
| Is This Answer Correct ? | 18 Yes | 2 No |
Post New Answer View All Answers
how you configure motorvision relay (L&T make)from DCS
What is a surge supressor why its is used in synchronous generators
why don't we use the generator as a motor? and what will happen?
Under wat condition statcom operates as an inductor for the transmission line?
Hi, My plant daily consumption is calculated as 3.8MWH but my supplier has sanctioned an power of 2.6MW per day. how can i equal or distinguish this two factors
why Y CONNECTION IS BETTER INTERMS OF EFFICIENCY AND P.F FOR A LAOD LESS THAN 40% AND WHY AFTER DELTA IS BETTER FOR > 40%
A 3 phase transformer's (Y-Y) Y and B phase is (Y and B connection not broken) broken from neutral and R and Nutral connection is ok, what will be the relay tripping and why
What is difference between Over Current & Earth Fault protection?
hello friends..... any one have papers or any study materials?sail ,hpcl...?
Thermal withstand capability under full short circuit conditions, in terms of number of times of occurrence of short circuit and corresponding anticipated percentage reduction in transformer life.
what is meant by carrier aided trip protection in transmission line
If two Transformers are connected in parallel having impedance of 50KA in both transformers will the impedance increase or decrease after connecting transformers in parallel?
how mass curve differs from hydrograph.
How would you relate your key competencies to this position?
What is called grain-oriented laminations?