why in three phase 440 circuit in all phase current is
almost equal L1-35 A,L2-34 A ,L3-31 A but in nutral when i
check with clamp meter it shows 25 A?
Answer Posted / kiran
Principle is vector summation.
Ir + Iy + Ib = 0
and not arithmatic summation.
Since neutral current is substantial 25A, the three RYB
vectors are not 120 degree apart. Means powewr factor in
each phase differs drastically. Thats why though there is
no much difference in RYB current, neutral has substantial
current.
| Is This Answer Correct ? | 18 Yes | 2 No |
Post New Answer View All Answers
Draw transformer phasor diagram.(full load,no load)
What is the difference between Delta & Wye windings?
why zero sequence impedance measurement is not applicable for single phase GT
How you will determine the volume of oil in a particular Distribution transformer.
how to select proper cable for ct wiring so that drop within the limit.
If Polarization index of motor 8.75 at 500volts of medium voltage 4.16 KV motor what this mean winding good or bad pl answer if any reffrence book give me the link
Can I use star delta connected induction motor for dual supply voltage?
What is difference between Sample test and Routine test in safety standard?
Why we make earth connection with Transformer Body and What will be the minimum size of copper wire as per code with respect to KVA rating of Transformer?
Why we used 690V in ACS 800 drives.Why dont use standard voltage like 415v or 1.1Kv
What is FTA card? How it works?
i have some screw comprressor with 630kw power,i have established them with simple star to delta circuit,by the way there is so much inertia when the screw comprressors start, can you offer me contactors power with 400vac or any cataluge to choose the contactors
If any HVDC line is going with positive & negative(the negative usually have return path of current with earthing electrode). Now the question is if this HVDC earthed electrode which is using as return path and earthed any nearby 400kv or 220kv AC substation equipments. which will be the impact of this on AC substation & its equipment, how severe may be this and what should be the minimum distance require between HVDC earthed electrode and AC substation equipments? It's really an high engineering level question...Dare to answer and increase your knowledge.
Explain what is electric traction?
What happen to the transformer if the OLTC frequently used for lower and raise occured 50times daily?