What is C.T, why it is used and what care should be taken
for that while connecting?
Answer Posted / bo
Care must be taken when selecting the Class of CT's. They have to be ordered specifically for their intended purpose. Metering CT's are highly accurate, but will saturate at network fault currents and cause maloperation if inadvertently used for protection.
CT secondary wiring must always have 1 ground connection, this is to prevent a dangerous voltage build up due to capacitive coupling from the Primary voltage which could be thousands of volts. (Ground connection is not required on LV installations below aprox 500V).
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
When lag/lead/lag-lead compensation is employed?
Why efficiency of generator is higher than motor at a particular load?
what is acceptance test in electrical engineering.
What is the difference between single point and double point bonding. please kindly detail about bonding of cables.
In the magnetic fluxes, what is the role of armature reaction?
Is it possible to measure correct value of earth resistance & cable insulation ristance with out disconncting earth lead & both sides of cable ends? If not, any other method to measure ER & CIR with out disconneting from the system.
What are operating procudures & Safety precautions to be observed while operating OLTC in manual mode ?
when we decide to use soft starter drive or vfd drive in mcc to operate apump?
How to calculate capacitor bank value to maintain unity power factor with some suitable example?
is it possible to test of bus bar in high rise building without completed full floor ?
what is a speed of rotor when we give supply to stator of 50hz and as well as rotor of 60hz of an induction motor?????
what ispositive, negative, zero sequence impedence?
What is Control & Relay Panel? And Remote Control Center?
If anyone would like to know or practice for FEWA papers contact me on mohamedrashad2@hotmail.com Just completed the supervisor exam in April 2021
I WANT TO know WHICH WAY IS BETTER FOR CONNECTION BETWEEN POWER TRANSFORMER AND MAIN DISTRIBUTION PANEL. 1-IS BETTER WE USE CABLE? 2-IS BETTER WE USE BUS DUCT? my transformer rate power is 2500KVA