Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

The armature of shunt dc motor has 0.8ohm resistance and motor
is to run on 120V circuit.If motor is suddenly thrown on
circuit while armature at standstill then current drawn by
motor will be??Also back emf in normal running is 110V

Answer Posted / muhammad waqas

V =Eb + IaRa
Ra= 0.8ohm
Eb=110V
V=120V
Put values in eqn
120-110=0.8Ia
10/0.8= Ia
Ia = 12.5 A

Is This Answer Correct ?    5 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

If you have an earth with pilecap then your resistance is really low. why and how?

1974


For a three phase induction motor, what will be the effect on motor if the neutral of the system is shifted to say 20 deg.?

1809


I just purchased a 4 position cam switch to be used to operate a 3-speed blower motor. The motor is a 10 amp motor and has 3 wires that are used to control speed. The cam switch was rated at 660V 20 amps but when I received it, I noticed that it has AC-15 operational current rating (Ie) of 4/5 amps. If I am reading the label correctly. the 4/5 amps is related to 440v/220V (Ue). Other ratings are AC-3: 5.5A, AC2: 7.5A and AC-4: 1.5A. My questions are 1) Is it safe to use this switch with the motor I have 2) what is the difference between the 20 amp Ith ratting and the Ie operational ratings?

1728


How many Zones can be in Conventional type fire alarm system & how can we detect the fire in Conv. type FAS?

1808


what is reactive power?, why its measured in VA ? is it transient behavior of system?

2285


why we use Test Terminal Block in 11 KV and 33 KV electrical panels.

1353


What is the diff. between single compression and double compression gland

1975


How to arrange a hous hold earthing system to keep minimum earth resistance( below 7ohms).

1940


How do we calculate the resistance per metre of single core aluminium stranded cable 19*3.25mm sheathed in pvc,at 15 deg C temperature?

2383


Application Comparison between 22KV (UE)and 33KV (E) system. Are we allowed to use 33KV (E) cable in lieu of 22KV (UE) cable. What are the technical disadvantages.

2803


Hi Suppose we have a wye/wye transformer which is grounded at both sides,in this situation, do we have ay ground transformer? in other words, ground transformer can do any thing more (while we have nuetral wire in both sides)? As the last question, what about 3rd harmonic? we have two choices: first using wye/delta transformer + ground transformer and second using wye/wye earthed connection.in the former choice, we dont have 3rd harmoonic at the secondary side but what about Yn/yn conection? do we suffer from 3rd harmonic in the Yn/yn connection?

1955


Why use in ht motore

1673


if any body have question paper of railway (section engineering),then plz send me .i will thank of him/her.

1982


How to work E.L.C.B and how to connect in circuit.

2002


which phase is preferred for connecting 1 phase vt used for synchronizing OHL? WHY?

2031