Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...


How to calcute the cable size for both HT and LT please
specify the formula for that

Regards
Chethan C

Answer Posted / kanchan dogra

Selection of HT cable is based on
1. short circuit calculation
2. Full load current capacity
1. Short Ckt. calculation
if total load is 3000 KVA, V 11 KV
short ckt MVA on HV side = 350 MVA (As per standard practice)
short ckt. current Ik= MVA/root3 x KV
350/root3 x 1= 18.4 KA
duration of short Ckt= 1 Second
cross section area of the conductor = Ik x root T/.094
18.4x root T/.094 = 95 SQ.mm

2. Full Load current
Total Load= 3000 KVA
System Voltage= 11 KV
Full load current = KVA/ root3 x KV
3000/root 3 x 11= 157 Amp.
derating factor = .7
current carrying capacity after derating = 157/.7 = 224.95 AMP.
Hence select cable for this current.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What should be the height of basement according to NBCC code?

2193


what is difference between earthingpits,earthing grid & earthing mess?

2501


What is quadrantal symmetry?

1642


Explain what is use of lockout relay in ht voltage?

1072


Why syn. Generators are used for the production of electricity?

1146


Explain forward resistance, static resistance and dynamic resistance of a pn junction diode.

1189


what are the steps involved in generator load test?

1546


Please clarify, 1. Is it required to lay two runs of GI wire along with Armoured LT cable if it is laid between one big mains (63Amps TPN SDF) to small main (32A TPN SDF) with proper glanding termination? 2. If the armoured cable with proper glanding is laid from DB to CNC machine, is it required to run two runs of body earthing to the Machine from DB? 3.If the armoured cable with proper glanding is laid from Substation to Hangar, distance is approx. 100 mtrs, is it required to do earthing at shop area though the primary termination at substation is earthed through gland.

2023


in 6.6 kv vaccum circuit breaker vaccum bottole vaccum capacity ????

1997


why ct's&pt'S out put called as burden,why compelsary short ckt the secondary of ct's while removing the burden?

2251


How to calculate or formula to calculate rhe power in 2 phase system ??

1498


Single line digram for 11 kV to distribution use go,la and do

1806


1.what is difference in maintain Hz again Hz in USA ? 2.how to calculate the battery AH? 3.why are yearly maintained in transformer how many tests in required?

2770


54 Comments Alok and Bhanu play the following min-max game. Given the expression N = 38 + X*(Y – Z) where X, Y and Z are variables representing single digits (0 to 9), Alok would like to maximize N while Bhanu would like to minimize it. Towards this end, Alok chooses a single digit number and Bhanu substitutes this for a variable of her choice (X, Y or Z). Alok then chooses the next value and Bhanu, the variable to substitute the value. Finally Alok proposes the value for the remaining variable. Assuming both play to their optimal strategies, the value of N at the end of the game would be?

2185


how many types are their in switchyard or substation(like D,I TYPE), what is differant between them

2108