Answer Posted / andu d
440V is the nominal voltage to compensate for the transformer internal impedance. i.e a transformer with 5% impedance will drop 5% volts at full load. So fully load the transformer will be at or around 418v. It also allows us to use the transformer tappings to compensate for supply discrepancies.
| Is This Answer Correct ? | 1 Yes | 0 No |