Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Why the rating of the HT breakers are in 1250 Amp, while
the load on the breaker is around 50 Amp. ?

Answer Posted / vikash kumar

HT breaker is sized based upon the fault current. Here 1250A is the fault current. 50A is the normal current and overload protection is provided by CT and over current relay.

Is This Answer Correct ?    0 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Work done in a free expansion process is

1156


Give some differences between open loop and closed loop?

1105


what will be happen if earth point is being used for as a neutral point for raw power , and same will be used for ups earthing

2076


In Indian Household, generally we receive 220V AC single phase supply. But AC has 2 phases, +ve & -ve. So in +ve half cycle current is flowing...so what happens in the -ve half cycle?? Please illustrate.

2025


if the load is 80 amp for main fuse and 100 amp for breaker so how can we calculate the cable size (cooper ) .

2069


What is the exact formula for one weber of magnetic flux?

2136


What is the tests required for a 132 kV, 400 kV , 765 kV for a Circuit Breaker and Power Transformer before commissioning ?

1560


tell me about eletrical contractor

1943


Is it required to lay 2 runs of GI wires along with armoured cables from one power DB Machines of higher rating?

1999


how to calculate transformer turn primary & secondary side 11kv to 420v

2192


induction 3 phase motor terminal connection

2657


What are the differences between single phase and three phase?

2033


what is the responsibility of C license holder in industry?

9154


mccb service sittings be done?

1804


WHY THE DIMENSION OF TWO SAME RATED MACHINE IS DIFFERENT ?

2159