Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Why short circuit calculation is not required in LT cable
sizing and requiredin HT cable sizing only

Answer Posted / sudhanva madhukar mahamuni

Generally LT Cable size are not calculated based on Fault current basis, Due to High Fault current on LT System. For e.g. consider that 2500 kVA Transformer, %Z = 6.25%, 415 Volts at Secondary. Fault Current at Secondary system will be 55.64 kA. Now if we would have to select the Cable size based on Fault current then it would be ---
If √t
A = ----------------- Sq.mm --- For XLPE Cable Aluminum Conductor
0.094

585 sqmm, nearest standard rating of cable is 630 sqmm. Hence Commercially as well as laying point of view the same is not recommended nor as per good engineering practice.

HT Cable Sizing :

Cable sizing based on Fault current is possible In HT System, based practically and commercially point of view. Consider that 11kV system is feeding the power supply. As per IS 2026, 11kV Power system will have max 500MVA Fault Level. It means it will have 26 kA. 300sqmm cable will be sufficient to withstand 26 kA for 1 Sec.

Summary : System Design shall not be strictly as norms, it should be design considering Laying / installation, Practically and Commercially viable.

Regards

Sudhanva Madhukar Mahamuni
electricmahamuni@gmail.com

Is This Answer Correct ?    2 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

i've iocl interview.. if you know the interview process please give me information..

2019


What will happen if i used 11KV earth ht kit to 11 KV / 11 KV cable termination?

1429


What is the drawback of class b amplifier? How is this minimized?

1139


Brief working principle of stabilizer,application & safety precautions

5696


If only R Phase is connected in 2 pole elcb, n is not connected than it will work or not in ground fault.

1442


Make a list observation on Transformer?

2436


power transmission pole used one support , that only for support or earthing

1964


Please, if 1kw is equal to 1.25kva; how then do I know how many kva in 7.5kw?

1667


Differentiate between magnetic field and magnetic flux?

1135


difference between semiconductor & conductor & insulator?

2381


What is K-rated transformer? What is the use of it? What can be the size(pls provide calculation if possible) of K- factor transformer for 550kW,690V motor operating with drive (VFD)?

2285


In constant power region of 3-phase IM torque-speed characteristics, if frequency increases flux A does not alter B decreases C increases D none of above

2251


What types domain of laplace transforms? What behavior can laplace transform predict how the system work?

1154


whate is the meaning of balance/unbalance,in stabilizers type

2140


what is ps impedance test

2139