Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I have 90KW Motor 60 Hz,380V Pf 0,88.
after testing the Motor without Load is the no load Current
36 A,but wenn i put load after 2 hours the current increase
more than 156 A.
Can anybode tell me waht is the Problem?

Answer Posted / ketan patekar

90 KW motor full load current carrying capacity is 236 ampere..
And yes when you connect load than afcourse your motor will carry ampere as per your load.
So here everything is ok.
If your motor carrying above 236 ampere current than there is some fault like your load is high or impeller or frame or design problem etc

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How to select the cable and voltage drop in circuit?

1830


why we use 630mm single core cable for transformer secondary side and why two neutral cable

1891


how the characterstics of control valve being done

2133


is it possible to start a motor in felid connected to a remote mcc

1974


i am completed my degree(B.E EEE) 2014 anychance to get electrical licence plz help me

2203


what is kvarh? Please define it With calculation General motors ?

1226


How can we findout the maximum efficiancy of Transformer? At which load?

2136


How halogen & merquery lamp works.

2223


Don't you have similar question banks related to Oral Certification Examination conducted by Mercantile Marine Departments / Directorate of Shipping, Ministry of Shipping for Electro Technical Officer?

1721


a)In a 3-phase 4-wire circuit, a circuit breaker is selected to protect the circuit whose highest fault level is 6.6 MVA. Determine the required minimum breaking capacity in kA. (Note: Covert 3-phase power in terms of kA to find answer.) b)Using the below, determine the required minimum making capacity in kA as a “peak value”. Rate breaking capacity (Icn) ka: Icn<= 1.5 Factor = 1.41 1.5

1749


What is the difference between single point and double point bonding. please kindly detail about bonding of cables.

2510


How much should be the load percentage for 15kva Inverter and Iinut & I output load with Calculations

2172


bsnl tta exam question

1934


What is difference between SMC supportg and Glass Fibre Reinforced Plastic Support.

2393


i need list of swg(standard wire guage) or area of conductor v/s current carrying capacity of conductor copper & alluminium...

1874