how to calculate the cable size for 500 kva transformer?
Answer Posted / ezhil
the full load amps of 500kva transformer is
kvax1000 / 1.732 x v
500x1000 / 1.732x415
500000/719 = 695A
Hence we can select 2R X 3C X 300SQMM
Is This Answer Correct ? | 15 Yes | 3 No |