Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How much current can 11KV line carry? What are the
formulae used to calculate current across both side of
transformer? Moreover I need to know can I connect 33KV
line with transformer of 1600KVA? Details are: V=415,
Pf= .9

Answer Posted / suhailpro

Primary side voltage be 11KV,
Transformer's capacity= 1000KVA

Real power= Apparent*Power factor
KW=KVA*Power factor
if Power factor = 0.95
Power= 1000*0.95
Power=950KW
We also know,
Power(KW)=(root 3)*(KV)*I*Power factor
950=1.732*11*0.95*I
I(Current)= 49.7A

Secondary Voltage Be 433V
We know that,
Power(watts)=(root 3)*V*I*Power factor
Power=950KW=950000W
950000=1.732*433*I*0.95
I= 1333.4 A

Is This Answer Correct ?    9 Yes 7 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how the characterstics of control valve being done

2133


Discuss the effect of sudden loading of an induction motor

1917


How to derive detailed design of Suitable bus Bar for 100A for 6.6KV?

1866


im working in one private compeny in gujarat. i was complet diploma electric in 2010 from gujarat technical board. now i want electric supervisor licence in gujarat but i dont't know when i apply? plz give me address of the licence dippartment office in gujarat. gandhinagar

1909


This is urgent!! What is a Thyristor-based 3-ways selector switch with Zero crossing control? how does it operate and where is it mostly found in a system?

2113


how can i get the formula to find out the cable size if i know the load of main fuse protection.

1980


In the Variable Voltage Variable Frequency Drive, how the Voltage and Frequency varied ? Is it varied in the Inverter part of the Drive ? Please give us supporting document if any.

1996


hi frenz,its aswathy.i hve aplied for the hpcl test on feb,pls send the test patern & the placement papers as soon as possible. mail-id :kjaswathy@gmail.com

1828


What is the difference between type1 and type2 relay protection co-ordination for motor feeders

2283


234 MVA Generator 3 phase Short circuit current Values required? Gen set Rating-234 MVA, Gen Voltage-18kv, PF;0.8, Xdv:23.5 %, Transformer Rating-18/380KV, 680MVA,Yndd1 two winding, Step up TR, ZT:35.50 %,X/R 4.33 Gen CB Position, CB open ,Disconnected open, Generator Running Voltage 18 Kv, Bi mistakes generator side earth switch Closed during that time short circuit current level in 3 Phase required, and how to test on site 234MVA Generator Short circuit current,

2090


I have 440v power coming to facility,( not being used ) can I buy large generator, (gas) to sell power back to electrical co.

2513


How does a tertiary winding filter harmonic(espcially 3rd one) from entering into load system?

1861


If we have 11 kv RYB Phase single core cable near about. Then wht effect and losses

1933


write encoder 17 pins details? pin a;b+, pin b;w+,..pin s & t. what is the meaning of b+, w+? explain;

2197


Inverter. converter. Ups.MCB.solar.alternators. motors.

2069