if the synchronizing b/w
generator and busbar not
complete and we close the
out going circuit breaker
of generator then what
happen ?
Answer Posted / milinda4p
IF the synchronization does not complete and if you close a cct breaker a severe arcing may occur and generator will trip instantaneously. Because the Generator sides voltages and bus side voltages do not match. To match the volatges following has to satisfied.
1. voltage magnitude
2. phase angle difference - 0
3. phase sequence - same
So at this condition there might be present voltage or phase angles or phase position mismatches. Say for example there exists a voltage magntude mismatch of 1 kV and when you close the cct breaker contact points have that voltage across them and this will cause severe current through contact points of breaker
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
The ripple frequency in output of fullwave bridge rectifier is a. Half the input b. Twice the input c. Same as input
How to select the proper VSD to operate high inertial load
which cable is used for 15 Hp monoblock pump 3phase and service wire Distance is 210 feet please tell me cable size Armaured
State the other types of Air Conditioners?
What is slope...? Explain slope 1 and slope 2...?
What is the difference between rulling span and wind span of of an Over Head Transmission Line?
How isolater function when installed inelectrical 440V wiring
how commomn gate triggering is given for TRIAC ? other thyristor wont be efffected?
Haw to check conductivity of budbar
How does a television work?
write encoder 17 pins details? pin a;b+, pin b;w+,..pin s & t. what is the meaning of b+, w+? explain;
How seriving & testing of the HT & LT breakers are done. What are the standard Ir values on which we can come to know the test is passed or failed?
How LT megger works ?
why 15 kw motor winding resistance is low then 5 kw motor winding resistance?
Why ground terminal is used in pot meter 10k ohms