What core magnetic balance test of transformer?
How to do this test in a three phase Star delta (star-LV,
Delta-HV) transformer?
How to measure and where to measure?
thanks and regards
Austin
Answer Posted / electrical in detail
(1) Core Balance or Magnetic Balance of a transformer is well needed. This test is carried out to determine inter turn faults or magnetic imbalance in transformer.
(2) It is very well known that each turn of the winding of a transformer is isolated from other turn through appropriate insulation. A properly designed transformer of 11 KV / 415 V means applying 11 KV on one side will produce 415 V on other side and vice versa. Now if insulation between turns of a winding loses their property, then turns of the winding are short circuited and this situation is called inter-turn fault.
(3) When an inter-turn fault occurs, magnetic property of transformer is imbalanced and this imbalance is conveyed to secondary side of the transformer as the two windings are connected magnetically. It means voltage that is produced by mutual induction will also get affected. To identify this imbalance, magnetic or core balance (in fact, imbalance) test is carried out.
(4) This test is generally performed on STAR side of the transformer. Forgetting the international nomenclature, let us name three leads of STAR side as R1, Y1 and B1 while that of other winding as R2, Y2 and B2.
B1 is kept opened. A supply of say 440 V is applied between R1 and B1. Next step is to measure various voltages between different phases:
V (R1-Y1) = V (R1-B1) + V(Y1-B1)
For example,
440 V = 250 V + 190 V
(5) As both the windings are connected magnetically, applying voltage to star winding will induce voltage on other winding. Induced voltage in other winding shall be in same proportion to applied voltage at star side. But if, any inter turn shorting is there, the voltage induced on the secondary winding will not be in proportion to the applied voltage.
This is an indicative test only. Accurate results can be obtained in conjunction with other tests.
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
what are the differences between 'exhaust fan', 'heavy-duty exhaust fan' & 'super heavy duty exhaust fan'. what are their power ratings ?
how to copy from plc ge fanuc versamax series,all input and output, adress, and printout.
How much pf maintan in dg set in 6o% load,when Dg runnig Neutaal Earthing removed what happen.
State magnitude criterion.
How to perform a DC resistance test In Alternator and their proceduces?
placement paper samples of mspl company
how test transfomer(3 phase75kva) by megger
What is the main cause of magnetism?
apti mainly on logical reasoning, verbal and non-verbal ability (70 percent) and remaining technical. I was in ee but technical had mech ques like on turbines and welding.
Why an ac solenoid valve attract the plunger even though we interchanges the terminal? Will the poles changes?
which is chemical used as in ro water what is difference betweeen multi grade filter&dual media filter
why steady state stability limit is greater than transient stability limit ? How it can be explained ?
1sq mm dc powr cable can carry how much dc currnt
How to check the Bushings of the transformer?
if a number of plc s are there then how many modbus to be used