how to claculate earth strip size for 1500kVA transformer
for neutral and body

Answer Posted / chandan tripathy

As per IS 3043, Cross Section Area of Earthing Conductor
(A) =(If x√t) / K
Where:
t = Fault current Time (Second).
K = Material Constant.
Example: Calculate Cross Section Area of GI Earthing Conductor for System has 50KA Fault Current for 1 second. Corrosion will be 1.0 % Per Year and No of Year for Replacement is 20 Years.
Cross Section Area of Earthing Conductor (A) =(If x√t) / K
Here:
If = 50000 Amp
T = 1 Second
K = 80 (Material Constant, For GI=80, copper K=205, Aluminium K=126).
• Cross Section Area of Earthing Conductor (A) = (50000×1)/80
• Cross Section Area of GI Earthing Conductor (A) = 625 Sq.mm
• Allowance for Corrosion = 1.0 % Per Year & Number of Year before replacement say = 20 Years
• Total allowance = 20 x 1.0% = 20%
• Safety factor = 1.5
• Required Earthing Conductor size = Cross sectional area x Total allowance x Safety factor
• Required Earthing Conductor size = 1125 Sq.mm say 1200 Sq.mm
• Hence, Considered 1Nox12x100 mm GI Strip or 2Nox6 x 100 mm GI Strips

Is This Answer Correct ?    25 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

wow to calculate the transformer rating(KVA)

1670


How to calculate the volumetric capacity of a oxygen & Nitrogen gas Cylinder if pressure is 145 kg/cm2 & water capacity of cylinder is 67 liters.

1720


how to modify DOL control panel into Delta Y connection?

1477


Why HT 11 KV Slipring Motors are connected in star ?

1760


Why do we need a separate control desk & PLC control panel in Boiler plant or coal handling plant? Can we provide cost effective Control desk cum PLC panel. Is there is an specific need for control desk.. kindly advice.

1860






What is the principle of HIGH SPEED DIRECT DRIVE MOTOR ?

1511


a starter used for squirrel cage induction motor?

1207


We need to current density & short circuit calculation at 65kA for aluminium & copper busbar.

1239


Difference between HRG and NGR. Are they both the same thing

3640


-What shall be short circuit current of LV switchgear for a 1000 kva, 11.415kv, 3 phase tranformer with 5% reactance.

1668


why most of junction box vendors providing T5/T6 Temp class jb's for T3 area any special reason?

1619


What is resolver and glass scale in CNC how they work?

1739


What tests should i carry over on a newly rewinded DC Generator with voltage rating of 38 volts and current rating of 350 amps, to certify that the machine is OK?

1422


What are the temperature elements?

706


what is the difference between ups & inverter

5474