For testing 33kv cable hipot testing. How much kv we have to
Apply .Give in details.

Answer Posted / ram sundar

For DC HIPOT = 1.414*(2E+1)
E=33/1.73=19.07
DC Hipot = 1.414*(2*19.07+1)
55.34kv approx 56Kv

Is This Answer Correct ?    8 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

power transmission pole used one support , that only for support or earthing

1423


how to calculate the fault in substation

1709


how we test a 3 phase motor on single phase supply....? HOW WE RUN A 3 PHASE MOTOR ON SNIGLE PHASE. supply for testing..? how we verify of a 3 phase motors 6 wire & name thame a1/a2/a3..b1/b2/b3 and c1/c2/c3 for connecting star delta starter ........i have only 1 phase supply ? help forum..........

4402


how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?

1678


I want single line diagram for AMF & DG syncronizing panel

6618






what is meant by twilight switches 7 where its applicable ?

1411


In our factory so many iron pillors are exists for supporting the shed/Hangar. If do more no of earthings at one piller instead of doing more earth pits in many locations and running earth strip around the hanger, I can save the money. Please suggest this method is acceptable as per Is specifications though the Earth resitance of the farthest piller is with in the limits as per IS specifications.

1642


A 2083kva AVR was tested, phase to ground shows continuity, what is the implications

506


What are PLC leader logic program method

1260


A ii kv 1200 A Breaker combination fixed in a cubicle. How many ampere Fuse is required? If fuse is not using, Why?

1495


how to calculate the cable current ratingand and how much of distance the rating will be ok will the distance is incresed what the action we take

1612


What is Antipumping Function & If we have C.T how we find the Ratio ?

1516


How to do maintenance of transformer feeder.

1341


i have total 8 dg sets for synchronizing and 2 buscoupler,1 sectoin dg no 1,2,3,and 2 sectoin dg no 4,5,6,and last section dg no 7,8 ....if buscupler no 1 and 2 is off mode ..than dg no 1,2,3,will synchroniz of another dg sets?

1345


On what basis do you decide the ONAN (Oil Natural air natural) or Dry type transformer for a project?

1159