For testing 33kv cable hipot testing. How much kv we have to
Apply .Give in details.
Answer Posted / ram sundar
For DC HIPOT = 1.414*(2E+1)
E=33/1.73=19.07
DC Hipot = 1.414*(2*19.07+1)
55.34kv approx 56Kv
Is This Answer Correct ? | 8 Yes | 0 No |
Post New Answer View All Answers
power transmission pole used one support , that only for support or earthing
how to calculate the fault in substation
how we test a 3 phase motor on single phase supply....? HOW WE RUN A 3 PHASE MOTOR ON SNIGLE PHASE. supply for testing..? how we verify of a 3 phase motors 6 wire & name thame a1/a2/a3..b1/b2/b3 and c1/c2/c3 for connecting star delta starter ........i have only 1 phase supply ? help forum..........
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?
I want single line diagram for AMF & DG syncronizing panel
what is meant by twilight switches 7 where its applicable ?
In our factory so many iron pillors are exists for supporting the shed/Hangar. If do more no of earthings at one piller instead of doing more earth pits in many locations and running earth strip around the hanger, I can save the money. Please suggest this method is acceptable as per Is specifications though the Earth resitance of the farthest piller is with in the limits as per IS specifications.
A 2083kva AVR was tested, phase to ground shows continuity, what is the implications
What are PLC leader logic program method
A ii kv 1200 A Breaker combination fixed in a cubicle. How many ampere Fuse is required? If fuse is not using, Why?
how to calculate the cable current ratingand and how much of distance the rating will be ok will the distance is incresed what the action we take
What is Antipumping Function & If we have C.T how we find the Ratio ?
How to do maintenance of transformer feeder.
i have total 8 dg sets for synchronizing and 2 buscoupler,1 sectoin dg no 1,2,3,and 2 sectoin dg no 4,5,6,and last section dg no 7,8 ....if buscupler no 1 and 2 is off mode ..than dg no 1,2,3,will synchroniz of another dg sets?
On what basis do you decide the ONAN (Oil Natural air natural) or Dry type transformer for a project?