Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

For a certain load i need 100kw load ,In that case what
rating mccb should i use?

Answer Posted / chintan patel

It can be different for DC , 1phase AC , 3 phase AC , systems,

Lets calculate for all ,

1 ) For DC ( you have not mentioned Voltage but considering 230 V )

100 kw means 100000 watt

formula for DC power p= vi

100000= 230xi

i=100000/230= 434 amp

we always use current rating of the mccb is 1.5 times of full load current so we can use 434x1.5= 652 amp.
( if system is not running on full load select 630 Amp MCCB, if its on full load select 800A )


2 ) For 1phase AC,

Power: P = V I cos phi ( cos phi is power factor is not known assume 0.8 )

100000 W = 230 x I x 0.8
I = 543 Amp

we always use current rating of the mccb is 1.5 times of
full load current.
mccb required 543 Amp X 1.5 = 815 Amp
select 800 Amp MCCB

3)

If load is 3 phase AC ,

Power P = sqrt(3) x V x I x cos phi

100000 w = 1.73 x 415 x I x 0.8
I = 174

we always use current rating of the mccb is 1.5 times of
full load current.
mccb required 174 Amp X 1.5 = 261 Amp

( if system is not running on full load select 250 Amp MCCB,
if its on full load select 315 A )

Is This Answer Correct ?    3 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

In a power conditoining unit (inverter) of a solar plant when we measure the d.c. current fed by different strings of solar plates to inverter, the current in the negative wire is less almost by 1 ampere to the current in its positive wire say current in positive wire 5 A , then current in negative wire of the same string is 4 A. Since the current entering should be equal to current leaving then why the current is noticably less in negative wire.

1651


is it possible to say motor horsepower number without seeing name plate(when name plate damaged)

2138


How to select, design,size & calculate for 11 KV/33KV/66KV/132KV/220 KV/440 KV circuit breaker for HT side of transformer protection/HT distribution protection?

2810


Define step response?

1251


How we can determine short circuiting current any plant and for example a plant which power generation is 415 volts and plant load is 500 kw.

2058


what is the mechanism of operation of brushless dc motor why is it more wexpensive then ordinary permanent magnet motors

2048


what is the criterion for selecting vector group of Transformers ? i mean how to decide vector group of Generator transformer, substation trasformer and transformer at consumer end

2415


explanation of mesh bus bars

2209


what is the maintaining Cf in UPS.

2431


i've iocl interview.. if you know the interview process please give me information..

2081


An automatic water heater is an example of which type of control system?

1224


how many single tension hardware are required on a double circuit transmission tower?

1981


how is the incoming cable size calculated for a given current rating of a panel??

1989


How to calculate the sag on transmission Lines.

3078


what is the condition for YnD11

2616