I want formula to calculate cable size as per load given in
kw & amp.I searched many sites but didn't right answer.Plz
reply me asap.

Answer Posted / hosam

you have 100kva pole type TX
POWER 100x0.8= 80 kw
total load aprox: p= 47 kw
tx capactiy rate 47/100 =% 47 load
the resistance of earthing to be less than 3 ohms.
cable cu 70 squ mm to load 47 kw lengh 100 mtr
%e1= 0.0124(47x100)/70= 0.85 tolal load
from tx to panels supply 32.5 kw lengh 50mtr cable 4cxm35 mm squ + 14.5 kw lengh 25mtr cable10 squ mm
%e2= 0.0124(32x50)/35= 0.56
%e3= 0.124(14x25)/10= 0.4
%e = %(0.85+0.56+0.4)= %1,81 < %3
total of the voltage drop is acceptable

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

HOW TO CALCULATE EARTHING SIZING?

1558


What is the function of electron gun used in crt?

598


how the testing of protection CT Testing done through Primary injection kit please describe in detail procedure...

1792


what's producer of XLPE cable laying in undergroung

1656


how much winding resistance of 0.75kw to 12.5kw 3ph sqwiralcage induction motor?

2444






how to calculate magnetic force genrated by a coil ?

1727


What is Percentage impedence of a transformer? why it is expressed at a percentage? what is the importance of percentage impedence in case of a transformer?

1432


How to check the Bushings of the transformer?

1263


what is difference between window type and wound type transformers?where we will use window type and wound type transformers?

1724


in dc shunt motor if field winding is shorted then

1367


Explain the method to keep noises low in a control system?

653


What do you mean by dependent and independent voltage sources?

601


What are the different types of hydro schemes?

671


HOW TO REDUCE POWER PLANT AUXILIARY POWER CONSUMPTION?

2999


Differentiate between digital phase converter and ordinary phase converter.

762