-200mmwc to 500mmwc range transmitter have there 4mA is -200 and 20mA is 500.what is the range in 12mA?

Answer Posted / rampal.m.

-200 for 4ma and 500 for 20ma so span 16ma for span 700 that why
16ma for 700
1ma for 700/16 so 12ma for 700/16 and multiply by12ma=525
this -200+525=325
ans is for 12ma
=325mmwc

Is This Answer Correct ?    0 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Explain PID controller tuning & any one method used for it.

7000


For crude application in floating roof tank, how to calibrate a DP Transmitter? How is the floating roof weight considered?

5004


how to calculate signal cable sizing? and multipair cable sizing??explain in brief?

1899


Why 4-20 amps is being used in instruments? Why cant we use any other range instead of 4-20 amps? Why only 4 amps is taken as lower limit and why 20 amps is taken as the higher limit?

1057


How d.p. Transmitter can be applied to open tank?

642






in mass flow meter what is drive friquancy ?

1623


where i can get training in INTOOLS and PDMS in Delhi-NCR OR north part of India. please reply with ur ans. at arunsamkaria@ymail.com

3060


How to Calibrate Flow Switch in field

762


can you provide me full detail about instrumentation in ONGC??

1750


i want to know the interview format fot gail, instrumentation. pls answer me in habib.sami1003@gmail.com

2656


i have been asked by QAFCO to appear for interview for thy post of Instrument Designer(INTOOLS)..i m engineering graduate with 5 years exp. in design engineering.Will this job profile suit me??i need all ur help n suggestions for thy same?

1796


In Safe Guarding test what means by "Failed to Danger" ?

1657


If relative y axis vibration sensor is by passed, and relative x axis and absolute sensor is left working. how much monitoring i would have risked?

1025


I m appointed as an automation trainee engineer in small firm in that I am only the one , my company give me a project on s7-200 as i m beginner I don't know how to program so please send me the helpful site so that I complete my project before deadline....please help me out in this critical situation.

1364


We Have Two Field bus Pressure Transmitters of Different Sensor Range (I.E One is of Lower range and Another is of Higher Range).Is same Process Line. My Question is Can i provide Saturation Limit to my field Bus Transmitter as We can provide Saturation current limit to HART Instruments. As During Low Pressure Both Working OK ,But During High Pressure, transmitter with Lower sensor range Goes to Fault mode as Beyond its Sensor Limit it can Measure, So may I provide Saturation point Some where to Suppress This Fault during High Pressure.

1140